Magnetrol Jupiter JM4 Safety Manual Download Page 4

4

 

ORI-652 Jupiter

®

 Model JM4 Magnetostrictive Transmitter – SIL Safety Manual

•  Table 3 is used to determine the achievable SIL as a function of 

the Hardware Fault Tolerance (HFT) and the Safe Failure Frac-

tion (SFF) for the complete safety function (Type B — complex 

components as per IEC 61508 Part 2) of which the level transmit-

ter is one component.

2.0  Level Measuring System

The diagram at left shows the structure of a typical measuring 

system incorporating the JUPITER Model JM4 transmitter. 

This SIL-rated device is only available with an analog signal 

(4–20 mA) with HART communications, and the measurement 

signal used by the logic solver must be the analog 4–20 mA 

signal proportional to the level.

•  For fault monitoring, the logic unit must recognize both high 

alarms (≥ 21.5 mA) and low alarms (≤ 3.6 mA).

•  If the logic solver loop uses intrinsic safety barriers, caution must 

be taken to ensure the loop continues to operate properly under 

the low alarm condition.

•  The only unsafe mode is when the unit is reading an incorrect 

level within the 4–20 mA range (> ±2% deviation).

•  MAGNETROL defines a safe failure as one in which the 

4–20 mA current is driven out of range (i.e., less than 3.8 mA 

or greater than 21.5 mA).

2.1 

Miscellaneous Electrical Considerations

Following are miscellaneous electrical issues to be considered in a 

safety system.

2.1.1  Pollution Degree 2   

The JUPITER Model JM4 transmitter is designed for use in a 

Category II, Pollution Degree 2 installation, which is defined 

by the non-conductive pollution of the sort where occasionally 

a temporary conductivity caused by the condensation must be 

expected.
This is the usual pollution degree used for equipment being 

evaluated to IEC/EN 61010.

2.1.2  Over-voltage   

The JUPITER Model JM4 transmitter has, as standard, 

over-voltage protection per CE requirements. When considering 

Hi-pot, Fast Transients, and Surge, this protection is to 1000 

volts (1KV). Therefore, there should be no unsafe failure modes 

up to 1 KV.

PACTware

TM

 with

Jupiter® x.x DTM

HART Modem

Actuator

Jupiter

®

 Model JM4

Logic

Unit

Summary of Contents for Jupiter JM4

Page 1: ...oftware v1 x Magnetostrictive Level Transmitter This manual complements and is intended to be used with the Orion Instruments Jupiter Model JM4 Magnetostrictive Level Transmitter Installation and Oper...

Page 2: ...lation 6 5 3 Skill Level of Personnel 6 5 4 Necessary Tools 6 5 5 Configuration 6 5 5 1 General 6 5 5 2 Configuration 7 5 5 3 Write Protecting Locking 7 5 6 Site Acceptance Testing 7 5 7 Recording Res...

Page 3: ...section of the wire alloy This in turn creates a vibratory disturbance which begins to travel through the wire at a very constant rate of speed The disturbance is later detected via a sensing device...

Page 4: ...operly under the low alarm condition The only unsafe mode is when the unit is reading an incorrect level within the 4 20 mA range 2 deviation MAGNETROL defines a safe failure as one in which the 4 20...

Page 5: ...e Description Files is also required if HART is used Manufacturer Code 56 hex Model JM4 Device ID 56DF hex device revision 1 DD revision 1 For device installations in a classified area the relevant sa...

Page 6: ...NOTE This SIL evaluation has assumed that the customer will be able to acknowledge an over or undercurrent condition via the Logic Solver 5 3 Skill Level of Personnel Personnel following the procedure...

Page 7: ...9 999 NOTE Default Password 0 Password disabled Refer to the Model JM4 Installation and Operating Manual Bulletin ORI 650 for additional information on password pro tection It is required that after c...

Page 8: ...o maintain the appropriate Safety Integrity Level of a Safety Instrumented System it is imperative that the entire system be tested at regular time intervals shown as TI in the appropriate standards T...

Page 9: ...esent Status Present Status should be OK b Review the EVENT HISTORY i Messages in the EVENT HISTORY must be investigated and understood ii Corrective actions should be taken for critical messages that...

Page 10: ...have evidence of excessive noise iv If possible compare to Echo curve from commissioning to assure that performance has not changed significantly c Choose the menu DIAGNOSTICS ADVANCED DIAGNOSTICS IN...

Page 11: ...e manufacturer that the level transmitter Magnetostrictive 4 20 mA Model JM4 511x xxx is suitable for the use in safety instrumented systems according to IEC 61511 1 if the safety instructions and fol...

Page 12: ...12 ORI 652 Jupiter Model JM4 Magnetostrictive Transmitter SIL Safety Manual...

Page 13: ...IL 2 HFT 0 Single Float SFF 93 1 PFDavg 1 97E 03 Dual Float SFF 91 9 PFDavg 1 96E 03 Proof Test Interval Annually refer to PFD Graph below 7 4 PFD Graph The resulting PVDAVG Graph generated from the e...

Page 14: ...Lifetime of Critical Components According to section 7 4 9 5 of IEC 61508 2 a useful lifetime based on experience should be assumed Although a constant failure rate is assumed by probabilistic estima...

Page 15: ...Safety Related Systems ANSI ISA 84 00 01 2004 Part 1 IEC 61511 1Mod Func tional Safety Safety Instrumented Systems for the Process Indus try Sector Part 1 Hardware and Software Requirements ANSI ISA 8...

Page 16: ...ry inspection finds the cause of the claim to be covered under the warranty If the trouble is the result of conditions beyond our control or is NOT covered by the warranty there will be charges for la...

Reviews: