Eclipse

®

Model 706 

F

OUndatIOn

fieldbus

Operating Manual

Software Version 1.x

High Performance, 4th Generation

Guided Wave Radar

Level Transmitter

Use in conjunction with

I&O manual BE 57-606

Summary of Contents for Eclipse 706

Page 1: ...Eclipse Model 706 FOUndatIOn fieldbus Operating Manual Software Version 1 x High Performance 4th Generation Guided Wave Radar Level Transmitter Use in conjunction with I O manual BE 57 606...

Page 2: ......

Page 3: ...Blocks 24 3 1 Integrator Block IT 24 3 2 Arithmetic Block AR 26 3 3 Input Selector Block ISEL 29 3 4 Signal Characterizer Block SC 30 4 0 Model 706 Transmitter Configuration 32 4 1 Configuration Infor...

Page 4: ...n which the two wires carry a single variable the varying 4 20 mA current a dig ital communications scheme such as FOUNDATION field bus considers the two wires as a network The network can carry many...

Page 5: ...be needed 1 2 1 FOUndatIOn fieldbus dd Revision table 1 3 Link Active Scheduler LAS The default operating class of the Eclipse Model 706FF with FOUNDATION fieldbus is a Basic device However it is capa...

Page 6: ...distributed along its entire length Therefore the stored energy during a fault will be less and more devices are permitted on a pair of wires Instead of the conservative entity model which only allows...

Page 7: ...algorithm inputs and outputs and a user defined name The Transducer Block TB output is available to the net work through the Analog Input AI blocks Refer to Section 2 3 for additional information on...

Page 8: ...ual mode the target mode the permitted mode s and the normal mode of operation of a block Target The mode to go to Actual The mode the block is currently in Permitted Allowed modes that target may tak...

Page 9: ...number which is 0x000156 DEV_TYPE The model number of the ECLIPSE Model 706 FF transmitter 0x0005 It is used by the Host System and other fieldbus interface devices to locate the Device Descriptor DD...

Page 10: ...ssing time that is free to process additional blocks SHED_RCAS The time duration at which to give up com puter writes to function block RCas locations SHED_ROUT The time duration at which to give up c...

Page 11: ...he COMPATIBILITY_REV is defined by the device developer and manufacturer In such device replacement scenario the DEV_REV value of the replaced device is equal or greater than the COMPATIBILITY_REV val...

Page 12: ...FD_FAIL_ALM Used to broadcast a change in the associ ated active conditions which are not masked for the FAIL alarm category FD_OFFSPEC_ALM Used to broadcast a change in the associated active conditi...

Page 13: ...WARE_VERSION Read only parameter that corre sponds to Hardware Version in the Transducer Block 2 3 Transducer Block The three TRANSDUCER blocks TB contained within the ECLIPSE Model 706 FF transmitter...

Page 14: ...sion level Please refer to the DD Revision Table Section 1 2 1 Please refer to Appendix B for a complete list of the three Transducer Block parameter sets 2 3 2 Password Parameters To change a paramet...

Page 15: ...ck The ANALOG INPUT AI block takes the ECLIPSE Model 706 FF input data selected by channel number and makes it available to other function blocks at its output The channel selections are 2 4 1 aI Bloc...

Page 16: ...Most common mode for target PV Either the primary analog value for use in executing the function or a process value associated with it OUT The primary analog value calculated as a result of executing...

Page 17: ...CK_ALM The block alarm is used for all configura tion hardware or system problems in the block ALARM_SUM The current alert status unacknowledged states unreported states and disabled states of the ala...

Page 18: ...suitable engineering units 3 The SIMULATE parameter is active 4 AI block MODE is O S out of service NOTE This can be caused by the Resource Block being OOS or the AI Block not scheduled for execution...

Page 19: ...ion etc the value displayed will not reflect the transducer measurement 2 4 3 1 AI Out Display Screens The Analog Input Block Out values can be conditionally displayed as part of the rotating home men...

Page 20: ...ffset 15 5 XD Scale EU at 0 0 XD Scale EU at 100 81 3 XD Scale Units cm Out Scale EU at 0 0 Out Scale EU at 100 81 3 Out Scale Units cm L Type Direct Probe Probe Length 111 cm 81 3 cm 0 cm 81 3 cm 0 c...

Page 21: ...3 for additional information on the SOFT_SIMULATION_DISABLE parameter in the resource block 2 5 PID Block The PID Function Block contains the logic necessary to perform Proportional Integral Derivativ...

Page 22: ..._HI_ALM The DV HI alarm data DV_HI_LIM The setting for the alarm limit used to detect the deviation high alarm condition DV_HI_PRI The priority of the deviation high alarm DV_LO_ALM The DV LO alarm da...

Page 23: ...igh and low scale values associated with OUT PV The process variable use in block execution PV_FTIME The time constant of the first order PV filter PV_SCALE The high and low scale values associated wi...

Page 24: ...les over time The block compares the integrated or accumulated value to pre trip and trip limits and generates discrete output signals when the limits are reached ST_REV The revision level of the stat...

Page 25: ...iscrete output TIME_UNIT1 Converts the rate time units in seconds TIME_UNIT2 Converts the rate time units in seconds UNIT_CONV Factor to convert the engineering units of IN_2 into the engineering unit...

Page 26: ...atus Good is PCT_INCL GOOD_LIM UNCERTAIN_LIMIT Sets the limit for PCT_INC OUT receives the status uncertain if PECT_INC UNCERT LIM OP_CMD_INT Operator command RESET Resets the totalizer OUTAGE_LIMIT T...

Page 27: ...the host for sorting alarms etc MODE_BLK The actual target permitted ad normal modes of the block Target The mode to go to Actual The mode the block is currently in Permitted Allowed modes that targe...

Page 28: ...oportional gain multiplier value for IN_2 BIAS_IN_3 The bias value for IN_3 GAIN_IN_3 The proportional gain multiplier value for IN_3 COMP_HI_LIM Determines the high limit of the com pensation input C...

Page 29: ...may be used in the host for sorting alarms etc MODE_BLK The actual target permitted and normal modes of the block Target The mode to go to Actual The mode the block is currently in Permitted Allowed m...

Page 30: ...to force a given input to be used UPDATE_EVT This alert is generated by any change to the static data BLOCK_ALM The block alarm is used for all configura tion hardware connection failure or system pro...

Page 31: ...the variable correspond ing to the x axis for display It has no effect on the block Y_RANGE The display scaling of the variable correspond ing to the y axis for display It has no effect on the block G...

Page 32: ...uickStart menu is available for Level Only applications 1 Refer to Section 4 5 for configuration menus for Interface Volume or Flow applications 2 These configuration steps are not necessary if the tr...

Page 33: ...he previous item in the menu branch DOWN moves to the next item in the menu branch BACK moves back one level to the previous higher branch item ENTER enters into the lower level branch or switches to...

Page 34: ...t may increase by a factor of 10 after the value has been incremented 10 times Down Decrements the displayed value If held down the digits scroll until the push button is released Depending on which s...

Page 35: ...longer password protected and any value in the basic user menus can be adjusted without entering a confirming password NOTE If a User Password is not known or has been misplaced the menu item New Pass...

Page 36: ...rement type from the following selections Level Only Interface Level Level Volume Flow HOME SCREEN The Home Screen consists of a slide show sequence of Measured Values screens which are rotated at 2 s...

Page 37: ...ghted over a parameter or menu will provide additional information about that item DEVICE SETUP Choosing DEVICE SETUP from the MAIN MENU will result in an LCD presentation as shown at left The small d...

Page 38: ...Rod Std 7YG Sngl Rod Std 7YJ Sngl Rod HTHP Cages 7YL Sngl Rod HP Cages 7YM Sngl Rod HP Tanks 7YN Sngl Rod HTHP Tanks 7YP Coax HP 7YS Coax Steam 7YT Coax Std 7Y1 Sngl Flex Std 7Y2 Sngl Flex Bulk 7Y3 S...

Page 39: ...Flow Home Screen Main Menu Device Setup Quick Start Identity Basic Config I O Config Display Config Advanced Config Factory Config Measurement Type Level Only Interface and Level Interface and Volume...

Page 40: ...le Type Linear Spline CUSTOM TABLE VALUES Up to 30 Pairs of Head Flow Data Reference Distance 11 8 inches to 100 feet 30 cm to 30 m Maximum Head calculated read only Maximum Flow calculated read only...

Page 41: ...de View Upr Thickness Interface and Level mode only Hide View Volume Volume and Level mode only Hide View Flow Flow mode only Hide View Head Flow mode only Hide View Distance Hide View NRTotalizer Flo...

Page 42: ...trength units Sloped End Dist used when Lvl Thresh Mode is Sloped 25 to 100 feet 7 to 30 m Ifc Lvl Thresh Mode Interface and Level only Auto Largest Fixed Value Ifc Lvl Thresh Value Interface and Leve...

Page 43: ...y Fid Threshold Value SZ Hysteresis Safe Zone Hysteresis not used when Safe Zone Alarm is None 0 to 100 feet 0 to 30 m PROBE TARGET Compensation Auto Probe Target Mode Off Run Calibrate Targ Calib Tic...

Page 44: ...06 DTM PACTware PC Program The ECLIPSE Model 706 offers the ability to perform more advanced diagnostics such as Trending and Echo Curve analysis using a PACTware DTM This is a powerful troubleshootin...

Page 45: ...aus tive list of Diagnostic Indicators which follow the NAMUR NE 107 guidelines NAMUR is an international user association of automation technology in process industries whose goal is to promote the i...

Page 46: ...categories Failure Function Check Out of Specification and Maintenance Required The FOUNDATION fieldbus version of the Model 706 trans mitter was implemented according to the Field Diagnostics Profile...

Page 47: ...el 706 diagnostic indicators showing their priority explanations and recommended remedies Priority 1 is highest priority Priority Indicator name default Category Explanation Remedy Context Sensitive H...

Page 48: ...nsitivity View Echo Curve 15 EoP Below ProbeEnd Failure End of Probe appears beyond Probe Length Check settings Probe Length Dielectric Range Sensitivity View Echo Curve 16 Safety Zone Alarm Failure R...

Page 49: ...7 OK Reserved for future use 31 Inferred Level Out of Spec Distance measurement calculated indirectly from probe elongation Level reading is only approximate Verify Level reading If incorrect compare...

Page 50: ...ame explanation pairs exceeds the available space a appears in the rightmost column of the last line indicating more text below In this situation the DOWN key scrolls the text up Similarly while text...

Page 51: ...owing table assigns the proposed values of these characteristics in order of decreasing priority for each of the diagnostic conditions and or device configurations NOTES 1 Only the highest priority st...

Page 52: ...limited Inferred Level Echo Strength Ifc Level Upper Thickness Ifc Echo Strength Probe Buildup Bad Device Failure Constant limited Totalizer Data Lost NR Totalizer R Totalizer Bad Config Error Not lim...

Page 53: ...Specific Constant limited TB Config Changed All PVs Good Non Specific Not limited Ramp Interval Error All PVs Good Non Specific Not limited High Elec Temp All PVs Good Non Specific Not limited Low Ele...

Page 54: ...ld is to be hard grounded only at one point close to the DCS In addition the cable shield can be capacitively grounded in multiple places to improve EMC protection Ensure all devices are on the live l...

Page 55: ...smitter FOUNDATION fieldbus Appendix A Block Mode Operation OOS Screens such as shown below which can be from a 475 Field Communicator NI Configurator AMS DTMs etc can be an indication that the block...

Page 56: ...Level 15 LEVEL_UNIT Level Unit 16 DISTANCE Distance 17 DISTANCE_UNIT Distance Unit 18 PROBE_MODEL Probe Model 19 PROBE_COATING Probe Coating 20 PROBE_MOUNT Probe Mount 21 PROBE_LENGTH Probe Length 22...

Page 57: ...POLARITY EoP Polarity 50 EOP_DIELECTRIC EoP Dielectric 51 COMPENSATION_MODE Compensation Mode 52 VAPOR_DIELECTRIC Vapor Dielectric 53 HF_CABLE_LENGTH HF Cable Length 54 BUILDUP_DETECTION Buildup Detec...

Page 58: ...E_TARGET_MODE Probe Target Mode 90 TARGET_CALIB_TICKS Target Calib Ticks 91 WINDOW_GWR Window 92 CONVERSION_FACTOR Conversion Factor 93 SCALE_OFFSET Scale Offset 94 M7YK_SCALE_OFFSET 7XK Scale Offset...

Page 59: ...Time 126 HIST_ENTRY1 Event History 1 127 HIST_ENTRY2 Event History 2 128 HIST_ENTRY3 Event History 3 129 HIST_ENTRY4 Event History 4 130 HIST_ENTRY5 Event History 5 131 HIST_ENTRY6 Event History 6 13...

Page 60: ...161 DATA_LOG_RECORDS Log Data 162 PD_TAG_APPL_IMAGE PD Tag Volume transducer Block table Item Parameter Name Parameter Label 0 BLOCK_STRUCTURE BLOCK STRUCT 1 ST_REV Static Revision 2 TAG_DESC Tag Des...

Page 61: ...e Pt 10 37 VOLUME_TABLE_PT_11 Volume Table Pt 11 38 VOLUME_TABLE_PT_12 Volume Table Pt 12 39 VOLUME_TABLE_PT_13 Volume Table Pt 13 40 VOLUME_TABLE_PT_14 Volume Table Pt 14 41 VOLUME_TABLE_PT_15 Volume...

Page 62: ...ameter Label 0 BLOCK_STRUCTURE BLOCK STRUCT 1 ST_REV Static Revision 2 TAG_DESC Tag Description 3 STRATEGY Strategy 4 ALERT_KEY Alert Key 5 MODE_BLK Block Mode 6 BLOCK_ERR Block Error 7 UPDATE_EVT Upd...

Page 63: ...Generic Eqn K Factor 40 GENERIC_EQN_L_FACTOR Generic Eqn L Factor 41 GENERIC_EQN_C_FACTOR Generic Eqn C Factor 42 GENERIC_EQN_N_FACTOR Generic Eqn n Factor 43 FLOW_TABLE_TYPE Flow Table Type 44 FLOW_T...

Page 64: ...Pt 25 70 FLOW_TABLE_PT_26 Flow Table Pt 26 71 FLOW_TABLE_PT_27 Flow Table Pt 27 72 FLOW_TABLE_PT_28 Flow Table Pt 28 73 FLOW_TABLE_PT_29 Flow Table Pt 29 74 FLOW_TABLE_PT_30 Flow Table Pt 30 75 ENTER...

Page 65: ...65 BE57 646 ECLIPSE Guided Wave Radar Transmitter FOUNDATION fieldbus Notes...

Page 66: ...66 BE57 646 ECLIPSE Guided Wave Radar Transmitter FOUNDATION fieldbus Notes...

Page 67: ...67 BE57 606 ECLIPSE Model 706 Guided Wave Radar Transmitter Notes...

Page 68: ...direct or consequential damage will be allowed RETURNED MATERIAL PROCEDURE So that we may ef ciently process any materials that are returned it is essential that a Return Material Authorisation RMA f...