32
48-640 E3 Modulevel
®
Displacer Level Transmitter - F
OUNDATION
fieldbus
™
display
Password
action
Comment
15
Run Time
xxxx.x h
None
Diagnostic Display showing
elapsed time since power on
or History Reset
Cleared to zero with History Reset
16
History
Reset
SuperUser
Press and select Yes to
clear history
17
MeasType
(select)
SuperUser
Factory Set
Select from Level, IfcLevel, or Density
18
Model
(select)
SuperUser
Factory Set
Select from E3A, E3B, E3C, E3D, E3E, E3F, E31, E32, E33,
E34, E35, E36, Custom
19
SpringSG
(select)
SuperUser
Factory Set
Select 0.29–0.54, 0.55–1.09, 1.10–2.20, HighPres, or
Custom
20
SprgRate
x.x
SuperUser
Factory Set
Only selectable when custom selected for SpringSG.
21
SprgMatl
SuperUser
Factory Set
Select Inc 600, Inc X750, 316 SS, UltraHiT
22
TempLimt
xxx F
SuperUser
Factory Set
Enter maximum process temperature for which unit is
suitable
23
Length
xx.xx lu
SuperUser
Factory Set
Enter length of measuring range (7 to 240 inches)
24
Diameter
x.xxx in
SuperUser
Factory Set
Enter outside diameter of displacer (0.5 to 5 inches)
25
Weight
xx.x oz
SuperUser
Factory Set
Enter weight of displacer and stem assembly
(40 to 200 ounces)
26
CalSelct
(select)
User
Select Factory or User
Calibration
Selects Calibration Parameters used to calculate the
measured PV.
27a
Factory Cal
Menu
None
Press to display the User
Calibration sub-menu
CalSelct = Factory
Submenu on page 33
27b
User Cal Menu
None
Press to display the User
Calibration sub-menu
CalSelct = User
Submenu on page 33
28
AdjSnrLo
None
Diagnostic Display
29
AdjSnrHi
None
Diagnostic Display
30
Conv Fct
xxxx
None
Diagnostic Display
31
Scl Ofst
xxx
None
Diagnostic Display
32
LVDT%
xx.xx %
None
Diagnostic Display
33
Chan 0
None
Diagnostic Display
34
Chan 1
None
Diagnostic Display
35
NodeAddr
SuperUser
Diagnostic Display
Current node address of device
36
NSP Value
SuperUser
Diagnostic Display
37
ElecTemp
xxx C
None
Diagnostic Display
Present temperature in electronics compartment
38
Max Temp
xxx C
SuperUser
Diagnostic Display
Maximum electronics temperature recorded
39
Min Temp
xxx C
SuperUser
Diagnostic Display
Minimum electronics temperature recorded
5.1
Measurement Type: Level Only (cont.)