The next set of conditions is the device warnings. The con-
dition will not jeopardize the level measurement. However,
knowledge of the condition may be useful in troubleshooting
the device.
The following table describes the conditions that can be
seen in Device Status:
display Message
action
Comment
OK
None
Normal operating mode.
User Access
Password at the local display.
Parameter values are being changed through the local interface.
Make sure Transducer Block is taken out of service.
Factory Access
Password at the local display.
Parameter values are being changed through the local interface.
Make sure Transducer Block is taken out of service.
Default Params
Internal non-volatile parameters have
been defaulted.
Consult factory.
Primary Fault
LVDT Primary circuit open condition.
Check LVDT winding resistance. Replace LVDT if values
are out of range.
Core Drop
• Core too far out.
• Bad LVDT wiring connection.
• Check for lost or damaged LVDT core.
• Check LVDT winding resistance.
Sec Fault Hi
• A/D readings from LVDT secondary
windings are above expected range.
• Bad LVDT wiring connection.
• Check for missing displacer.
• Check LVDT winding resistance.
Sec Fault Lo*
• A/D readings from LVDT secondary
windings are below expected range.
• Bad LVDT wiring connection.
• Check for broken spring or leaking displacer. This fault disabled
when measurement type is interface or density.
• Check LVDT winding resistance.
Default Cal
Factory set default calibration
parameters are in use. Level
reading may be inaccurate.
Consult factory.
Hi Temperature
Present temperature in electronics com-
partment is above 80 C.
1) Transmitter may need to be moved to ensure ambient
temperature is within specification.
2) Change to remote mount transmitter.
Lo Temperature
Present temperature in electronics
compartment is below - 40 C.
1) Transmitter may need to be moved to ensure ambient
temperature is within specification.
2) Change to remote transmitter.
Cal Span
Span between Sensor Calibration
Hi and Lo values is less than
minimum span.
Recalibrate or reconfigure unit with longer span
Initializing
None
Program is initializing. This is a transient condition.
*
Can occur when unit is designed for interface and no liquid is on the displacer.