Operating Instructions
581E,5811_07
28
If the person begins to pass and the center column is out of its home position,
the hold-open-time is set to an unlimited period of time.
When the center column is turned over 60°, the hold-open-time will be cleared
immediately. Furthermore the center column cannot be turned reverse.
In this mode, any other open pulse will be ignored, as long as the passage is
not finished.
11.2 Bidirectional pulsed operation with impulse storage
This operation mode works similar to the “pulsed operation without impulse
storage”. The only difference is that the controller can store up to 4 open
pulses for each direction and process one after the other.
If open pulses for both directions are stored, both directions are free.
The hold-open-timer begins to count down.
The center column can be operated left or right; independent from the order of
the open pulses.
After finishing the passage, the next passage can be started as long as open
pulses are stored.
By means of the relay outputs “blocked/free left”, respectively
“blocked/free right” it is possible, to indicate the free direction(s).
If the person begins to pass and the center column is out of its home position,
the hold-open-time is set to an unlimited period of time.
When the center column is turned over 60°, the hold-open-time will be cleared
immediately. Furthermore the center column cannot be turned reverse.
When the locking delay time is activated, the center column will be blocked
after each passage for approximately 1 second in its home position, before
the next stored pulse can be processed.
This is to avoid, a rotation of more than 120° per passage.
11.3 Permanent free in both directions.
If both inputs, IN1 and IN2 are switched by permanent contact (>2.5 s),
passage is free for both directions.
In case permanent contact is given to the inputs in pulsed operation mode,
stored opening pulses will be cleared.
If the locking delay time is activated, the center column will be blocked for
approximately 1 second in its home position, after each passage.
This is to avoid a rotation of more than 120° per passage.
When the permanent-open-contact (>2.5s) is switched off, the gate will be
blocked immediately. There is no hold-open-time active.