10. Adjustable parameters
The following parameters can be adjusted by means of DIP switches and
the trimming potentiometer:
DIP
Function OFF
ON
1 Barrier
type
MPT MPP
2
Pulse storage
Off
On = 4 pulses per
direction
3
Locking delay time
Off
On = 1 sec.approx.
4 Hardware
tests
*) *)
5
Hardware tests
*)
*)
6
Solenoid left in case of
power failure
blocked free
7
Solenoid right in case of
power failure
blocked free
8
Hold-open-time via LEDs
Not displayed
displayed
DIP 1
Selection of Gate type
This switch has to be set OFF(MPT)
DIP 2 Pulse storage
In case the function is switched OFF, only one demand pulse can be
processed. Further pulses are then ignored.
In case the function is switched ON, max. 4 demand pulses per passage
direction can be stored.
DIP 3 Locking delay time
The locking delay time can be activated via DIP 3, in order to avoid, that the
center column continues its rotation after passage of a person. This we
recommend in case of pulse storage (DIP 2 ON) or if one or both directions
are permanent free.
DIP 4 / 5 Hardware tests
The settings of these dip switches may only be changed after consultation
with Magnetic Autocontrol. Originally, both must be set “OFF”.
DIP 6 / DIP 7 “Free” / “locked” in case of power failure
Depending on the requirements of the application in question it is necessary
to assure free passage in one or either direction in case of power failure.
The mechanical installation and logic control unit of the two solenoids have to
be done in accordance with these requirements.
If a passage direction should be blocked in case of power failure, the
respective solenoid has to be built-in crosswise to the mounting plate (
Fig.20
).
DIP 6 respectively DIP 7 has to be set “OFF” in this case.