Figure 5: Typical 120VAC Power Wiring
Notes:
1. Although the power module has built-in protection, Magnetek strongly recommends the use of
external fuses and circuit disconnects for all Flex Modules.
2. The built-in fuse is not user-serviceable but can be checked if troubleshooting. To check the
fuse, remove the power module from the din rail as described in Section 2.3. After removing the
module from the din rail, press in the tabs as noted above to remove the PCB from the housing.
The fuse location is shown in the PCB view above. Use a multimeter to check for continuity
across the fuse. If the fuse is blown, contact Magnetek to send the module in for service.
3. The total system Current Consumption should not exceed the Maximum Output Supply Current of
1000mA. If additional supply current is required, contact the factory for a custom solution.
120VAC (L)
120VAC (N)
120VAC (L)
120VAC (N)
Not Used
Not Used
Not Used
GND