Page 12 of 21
507858-01
Issue 1922
Model
Gas Heating
Indoor
Blower
Speed
0.1 “w.c.
0.2 “w.c.
0.3 “w.c.
0.4 “w.c.
0.5 “w.c.
Rise
Range
(F°)
Mid
Rise
(F°)
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
3 T
on
24MGE4-1
1-361*P
25-55
40
TAP 1
(FAN)
615
82
---
580
86
---
540
91
---
500
96
---
450
102
---
TAP 2
(COOL)† 1020 307
---
980
313
---
940
314
---
900
318
---
865
323
---
TAP 3
(COOL)
1040 329
---
1000 329
---
965
333
---
930
338
---
890
344
---
TAP 4
(HEAT)*
450
48
40
385
52
46
325
55
55
N/A
N/A N/A
N/A
N/A N/A
TAP 5
(HEAT)
N/A
N/A N/A
N/A
N/A N/A
550
107
33
500
112
36
450
117
40
36MGE4-1
1-361*P
30-60
45
TAP 1
(FAN)
615
82
---
580
86
---
540
91
---
500
96
---
450
102
---
TAP 2
(COOL)† 1020 307
---
980
313
---
940
314
---
900
318
---
865
323
---
TAP 3
(COOL)
1040 329
---
1000 329
---
965
333
---
930
338
---
890
344
---
TAP 4
(HEAT)*
615
82
44
580
86
46
540
91
50
500
96
54
460
102
58
TAP 5
(HEAT)
N/A
N/A N/A
710
129
38
685
135
39
650
140
41
615
145
44
48MGE4-1
1-361*P
35-65
50
TAP 1
(FAN)
615
82
---
580
86
---
540
91
---
500
96
---
450
102
---
TAP 2
(COOL)† 1020 307
---
980
313
---
940
314
---
900
318
---
865
323
---
TAP 3
(COOL)
1040 329
---
1000 329
---
965
333
---
930
338
---
890
344
---
TAP 4
(HEAT)*
715
135
50
675
142
53
640
148
56
600
155
60
560
162
64
TAP 5
(HEAT)
N/A
N/A N/A
820
212
44
785
219
46
745
227
48
715
234
50
60MGE4-1
1-361*P
40-70
55
TAP 1
(FAN)
615
82
---
580
86
---
540
91
---
500
96
---
450
102
---
TAP 2
(COOL)† 1020 307
---
980
313
---
940
314
---
900
318
---
865
323
---
TAP 3
(COOL)
1040 329
---
1000 329
---
965
333
---
930
338
---
890
344
---
TAP 4
(HEAT)*
825
175
54
790
179
57
755
185
59
720
191
62
690
197
65
TAP 5
(HEAT)
935
240
48
905
246
49
870
254
51
845
260
53
815
266
55
N/A: Do not operate unit using this blower speed at this external static pressure.
† As shipped speed for Cooling operation. Blower speed must be field adjusted to speed Tap 3 for higher duct static applications.
* As shipped speed for Heating operation. Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications.
Table 4.
Blower Performance (208V or 230V)