background image

507858-01

Issue 1922

Page 5 of 21

2.  For U.S. installations, the vent system shall terminate 

a minimum horizontal clearance of 4’ from electric 

meters, regulators, and relief equipment. For 

installations in Canada, refer to the current CAN/

CGA-B149.1 & .2 or with the authorities having local 

jurisdiction.

3.  Flue products from properly adjusted and maintained 

units, will not cause degradation to building materials.

The unit contains an exhaust blower. The blower draws the 

combustion products out of the heat exchanger together 

with dilution air and forces the mixture from the unit to the 

outside. No special provisions are required for supplying 

air for combustion, nor is a chimney required.

The vent outlet must be extended (see Vent Pipe 

Installation).

The venting system is designed for proper operation under 

all weather conditions and for winds up to 40 miles per 

hour, and should be unobstructed for a minimum of 2 feet.

Existing Venting Systems

When an existing furnace is removed and replaced, the 

MGE4 unit venting system may no longer be sized to 

properly vent the attached appliances. An improperly sized 

venting system can result in spillage of flue products into 

the living space, the formation of condensate, leakage, etc. 

Refer to the 

WARNING

 box in the next column for proper 

test procedure.

Vent Pipe Installation

Determining the length of the vent pipe extension is 

dependent upon which wall sleeve accessory is installed 

at the job site for each particular installation.

For proper operation, the vent length must be correct for 

the installation. The unit may not operate correctly with 

inadequate vent length.

 CAUTION

1.  Access vent pipe at the side of the unit that will face 

the outdoors.

2.  The vent pipe and vent pipe extension is located to the 

right of the outdoor fan (see Figure 3).

Figure 3. 

Locating Vent Pipe and Extension

Mounting

Bracket

Vent Pipe

Outdoor Fan

3.  Remove the 5/16” screw used to mount the vent pipe 

assembly to the mounting bracket. Keep this screw.

Carbon Monoxide Poisoning Hazard

Failure to follow the steps outlined below for each 

appliance connected to the venting system being 

placed into operation could result in carbon monoxide 

poisoning or death.
The following steps shall be followed for each appliance 

connected to the venting system being placed into 

operation, while all other appliances connected to the 

common venting system are not in operation:

1.  Seal any unused openings in the common venting 

system.

2.  Visually inspect the venting system for proper size 

and horizontal pitch, as required in the National 

Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest 

edition) or the CSA B149.1, Natural Gas and 

Propane Installation Codes and these instructions. 

Determine that there is no blockage or restriction, 

leakage,  corrosion,  or  other  deficiencies  which 

could cause an unsafe condition.

3.  As far as practical, close all building doors 

and windows between the space in which the 

appliance(s) connected to the venting system are 

located and other spaces in the building.

4. 

Close fireplace dampers.

5.  Turn on clothes dryers and any appliance not 

connected to the venting system. Turn on any 

exhaust fans, such as range hoods and bathroom 

exhausts, so they are operating at maximum speed. 

Do not operate a summer exhaust fan.

6.  Follow the lighting instructions. Place the unit being 

inspected in operation. Adjust the thermostat so 

appliance is operating continuously.

7.  Test for spillage from draft hood equipped 

appliances at the draft hood relief opening after 5 

minutes of main burner operation. Use the flame of 

a match or candle.

8.  If improper venting is observed during any of the 

above tests, the venting system must be corrected 

in accordance with the National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 (latest edition) and/or the 

CSA B149.1, Natural Gas and Propane Installation 

Codes.

9.  After it has been determined that each appliance 

remaining connected to the venting system properly 

vents when tested as outlined above, return doors, 

windows, exhaust fans, fireplace dampers, and any 

other gas-fired burning appliance to their previous 

conditions of use.

 CAUTION

Summary of Contents for MGE4 Series

Page 1: ...aving jurisdiction should be consulted before installation is made Such applicable regulations or requirements take precedence over the general instructions in this manual CAUTION P507858 01 P 507858...

Page 2: ...NING Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components Only trained and qualified service personnel should i...

Page 3: ...lle accessories for safe operation Improper installations could result in property damage personal injury or death Minimum Unit Clearance Front Sides 1 1 Added clearance must be provided for the gas s...

Page 4: ...protection clearances There is no minimum clearance required on locating the unit to an interior corner of a building If the unit is installed in a residential garage it must be located or protected...

Page 5: ...the mounting bracket Keep this screw Carbon Monoxide Poisoning Hazard Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could re...

Page 6: ...make sure that the proper louver kit is installed Due to the high temperatures of the combustion products released from the gas vent MGE gas package units require the use of either an aluminum louver...

Page 7: ...c 0 4 w c 0 5 w c Rise Range F Mid Rise F SCFM Watts Temp Rise SCFM Watts Temp Rise SCFM Watts Temp Rise SCFM Watts Temp Rise SCFM Watts Temp Rise 3 4 Ton 15MGE4 11 091 P 15 45 30 TAP 1 FAN 430 46 370...

Page 8: ...N A TAP 3 COOL N A N A N A N A 475 93 430 97 385 101 TAP 4 HEAT 450 50 40 405 53 44 355 57 50 N A N A N A N A N A N A TAP 5 HEAT N A N A N A N A N A N A 525 101 34 485 105 37 450 110 40 36MGE4 11 121...

Page 9: ...N A N A TAP 3 COOL N A N A 765 184 730 191 675 201 630 206 TAP 4 HEAT 590 86 45 555 90 48 515 95 52 475 99 56 N A N A N A TAP 5 HEAT 715 129 38 680 135 39 650 140 41 615 146 44 585 151 46 48MGE4 11 18...

Page 10: ...224 TAP 3 COOL 910 273 880 278 850 283 820 287 785 286 TAP 4 HEAT 600 89 45 560 93 48 520 96 52 485 100 56 N A N A N A TAP 5 HEAT N A N A N A 700 148 38 665 153 40 635 157 42 600 162 45 48MGE4 11 241...

Page 11: ...38 670 141 40 635 146 42 600 151 45 48MGE4 11 301 P 35 65 50 TAP 1 FAN 490 55 465 65 435 72 415 81 390 89 TAP 2 COOL 930 239 900 243 885 250 835 256 805 262 TAP 3 COOL 1030 309 995 316 965 321 930 325...

Page 12: ...38 685 135 39 650 140 41 615 145 44 48MGE4 11 361 P 35 65 50 TAP 1 FAN 615 82 580 86 540 91 500 96 450 102 TAP 2 COOL 1020 307 980 313 940 314 900 318 865 323 TAP 3 COOL 1040 329 1000 329 965 333 930...

Page 13: ...Use thread sealant on the threaded fittings Install threaded fittings by hand only Do not over torque the fittings CAUTION Figure 6 Condensate Drain Installation Electrical Connections All wiring must...

Page 14: ...r Fan Access Panel to Gas Valve and Burners Access Panel to Controls Manual Shutoff Valve with 1 8 NPT Plugged Tapping Accessible for Test Gauge Connection Field Supplied Filter Access Any conversion...

Page 15: ...ed through flame sensor 5 Circulating air blower starts 30 seconds after the burners light 6 When the thermostat is satisfied the burners and combustion blower shut off 7 Circulating air blower will s...

Page 16: ...he proper speeds have been preset at the factory for typical heating and cooling operation Refer to the wiring diagram for recommended heating cooling speeds for specific models Speeds may require adj...

Page 17: ...tions which may contain chloride sulfites dust ammonia etc more frequent cleaning is required 2 Make sure there are no leaks of outside air into the return air system 3 Keep the outside louver grille...

Page 18: ...6 16 5 8 32 7 8 for 45 Louver ASLEEVE6 5 6 45 16 16 5 8 45 1 8 8 Wall Sleeve Kit for 29 Louver ASLEEVE8 1 8 29 16 16 5 8 29 1 8 for 33 Louver ASLEEVE8 2 8 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASLEEVE...

Page 19: ...29 Height ALVRAL 1 Extruded Aluminum Louver Kit Custom Color 29 Height ALVRAL 1P Extruded Aluminum Louver Kit 33 Height ALVRAL 2 Extruded Aluminum Louver Kit Custom Color 33 Height ALVRAL 2P Extruded...

Page 20: ...Page 20 of 21 507858 01 Issue 1922 Figure 9 Wiring Diagram 3 4 Ton through 2 Ton Wiring Diagrams...

Page 21: ...507858 01 Issue 1922 Page 21 of 21 Figure 10 Wiring Diagram 2 1 2 Ton and 3 Ton...

Reviews: