![Magellan MG5000 Programming Manual Download Page 38](http://html2.mh-extra.com/html/magellan/mg5000/mg5000_programming-manual_3420243038.webp)
38
Programming Guide
Connecting Fire Circuits and PGMs
N.C. Contacts, with EOL Resistor, with Tamper and Wire Fault
Recognition (UL/cUL)
Parallel Wiring
Program the PGM with the
“
[
]
Key was pressed”
Activation Event so that
the smoke detectors can
be reset by pressing the
[
CLEAR
] + [
ENTER
]
keys for
three seconds. See Event
Group # 6 on page 14.
All 4-wire smoke
detectors must be
connected using the
daisy chain
configuration
Each MG5000 control
panel supports a
maximum of five
2-wire smoke
detectors