Macurco CD-6B Manual (Rev-1.0) Eng
REV – 1.0
[34-2900-0510-2 ]
21
|
P a g e
4.8.15
Select Automatic Background Calibration – “Abc”
Available options are “OFF”, “On”.
NOTE
: This setting cannot be changed when unit is in Calibration Due or Calibration Overdue (“t 80” error code).
To select the Automatic Background Calibration setting, in normal mode:
1.
Push the
Next
button to get to “Con” or the Configuration menu.
2.
Push the
Enter
button to enter the Con menu.
3.
Push
Next
14 times (15 times if current setting is “OFF”) to get to “Abc” or Automatic Background
Calibration.
4.
Push
Enter
. The display will show the current setting.
5.
Push
Next
to cycle through the available settings (display will begin flashing).
6.
Push
Enter
to confirm the new setting (display will stop flashing).
7.
Push
Enter
once more to return to the configuration menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
4.8.16
Calibration Period – “CAL”
This option is
only available when “Abc” is turned “OFF”
.
The value selected in Calibration Period settings is number of months. The CD-6B indicates a “calibration due” when
it is within 1 month of the calibration period, and “calibration overdue” when the detector has reached or exceeded
the calibration period. The Calibration Period Settings cannot be changed if the CD-6B is indicating “calibration due”
or “calibration overdue”.
To select the Calibration Period Option, in normal mode:
1.
Push the
Next
button to get to “Con” or the Configuration menu.
2.
Push the
Enter
button to enter the Con menu.
3.
Push
Next
14 times to get to “CAL” or Calibration Period setting.
4.
Push
Enter
. The display will show the current setting.
5.
The default setting is “dIS”. Push
Next
to change it to 3, 6, 12 or 24 (flashing).
6.
Push
Enter
to confirm the change (solid).
7.
Push
Enter
again to return to “CAL” in the Con menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
5
Troubleshooting
5.1
On-Board Diagnostics
The CD-6B monitors all critical functions of the unit through software diagnostics that continuously test and verify
unit operations.
5.1.1
Trouble Condition
If a problem is found, the unit will switch to a fail-safe/error mode or trouble condition. In this error mode, the
•
Alarm 1 Relay will be activated if tFS is On.
Summary of Contents for CD-6B
Page 32: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 32 P a g e 9 2 Auto Test bUZ Menu ...
Page 33: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 33 P a g e 9 3 Configuration CON Menu ...
Page 34: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 34 P a g e ...
Page 35: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 35 P a g e ...
Page 36: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 36 P a g e ...
Page 37: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 37 P a g e ...
Page 38: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 38 P a g e ...
Page 39: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 39 P a g e 9 4 Select Test tst Menu ...
Page 40: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 40 P a g e 9 5 Calibration CAL Menu ...
Page 41: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 41 P a g e 9 6 Sensor Reset SEN Menu ...