Mac Victor 2.0 Installation Operation Manual 042408.pdf - © 2008 Mac Victor Power, LLC.
Page 9 of 23
4 – INSTALLATION
4.1 Package Contents
The packing box contains a Mac Victor 2.0, mounting hardware (wood stud mount only), a circuit polarity plug
tester, safety outlet protector plugs (12), UPS strapping materials, and this Installation and Operating Manual.
Carefully inspect all the contents. If any damage is visible immediately notify the carrier and the shipper.
4.2 Location
Please refer to Section 1.3 of the Important Safety Instructions regarding installation. Typical wall mounted
locations include the manager’s office, electrical room or closet, telecom equipment wall, datacom room, or other
secure locations that are not accessible to the public.
To minimize the distance of branch circuit runs to the remote Isolated Ground receptacles, choose a relatively
central location if possible to mount the Mac Victor 2.0.
A location relatively close to a circuit breaker panel is also preferred since a single 120Vac, single phase circuit
(Line, Neutral, and Ground) must be run to feed the input terminals of the Mac Victor 2.0.
Allow for UPS mounting height on top of the Mac Victor 2.0 when locating the height of installation.
4.3 Typical Elevation
The Mac Victor 2.0 Typical Elevation below provides a conceptual diagram of a typical wall mounted elevation that
shows the overall enclosure dimensions and typical input and output power wiring.
Figure 4.1 – Mac Victor 2.0 Elevation