Mac Victor 2.0 Installation Operation Manual 042408.pdf - © 2008 Mac Victor Power, LLC.

 

 

 Page 6 of 23 

 

2.3  System Benefits 

• Provides clean and continuous power for critical electronic systems to minimize downtime and lost revenue 
associated with computer lockups, data losses, hardware failures and power outages. 
• Centralized, wall mounted design saves valuable floor space and is easier to maintain and manage. 
• Eliminates the need for all remote plug in battery backups, filters, power conditioners, and surge strips which 
saves under counter / desktop space. 
• Assures that all connected equipment is on the same electrical phase of power for better data communication. 
• UPS Bypass Switch (make before break) provides seamless power during UPS maintenance 
• Input and output power pilot lights provide for status indication and ease of troubleshooting 

2.4  Description of Operation 

• 120 Vac, 1 Phase input power supplied to Mac Victor 2.0 from remote supply 

(20A for 2kVA or 30A for 3kVA circuit)

 

• Input circuit breaker provides overcurrent protection for Mac Victor 2.0 

(20A for 2kVA or 30A for 3kVA circuit)

 

• Input Surge Protection Device (hereafter SPD) replaceable module protects Mac Victor 2.0 from surges 
• Front Panel mounted Monitor detects open fuses on both Input SPD & Output Surge & Filter Board Assembly 
• Input power status light is illuminated when the input circuit breaker is turned on 
• Power routed within Mac Victor 2.0 to the Normal / Bypass transfer switch 
• In Normal mode: 

• Power routed from Normal/Bypass switch to the Mac Victor 2.0 Power receptacle and UPS plug assembly 
• UPS provides 120 Vac output with battery backup to UPS receptacle 
• Mac Victor 2.0 plug assembly connects to UPS receptacle and returns power back to the Mac Victor 2.0 
• Power routed through remote power off relay to the Isolation Transformer with neutral to ground bond 
• Output Surge & filter board assembly provides additional surge power protection and noise filtering 
• Output Surge & filter board assembly provides signal relays for Input and Output Power remote status 
• Output Surge & filter board assembly provides supply power & fuse status signal to panel monitor 
• Output power status pilot light is illuminated 
• Power routed to 4 output circuit breakers and terminals for field wiring to remote IG power circuits 
• (Optional) Power routed to 1 output circuit breaker that powers 4 fully integrated IG receptacle outlets  
• (Optional) Remote power off shutdown relay can be added for the integrated IG receptacles  
• Mac Victor 2.0 provides dedicated, fully isolated, battery backup source to remote hardwired Isolated 
Ground (IG) receptacles and other hard wired equipment 

• In Bypass Mode: 

• Power is routed from Normal / Bypass switch directly to remote power off relay, bypassing the UPS 
• Power is disconnected from the Mac Victor 2.0 Power Plug assembly in the bypass mode 
• Output power status pilot light remains illuminated and does not flicker during the transfer since the   
switch has “make before break” capability 
• Power is routed through the isolation transformer and through the circuit breakers to the isolated ground 
receptacles the same as in the Normal Mode operation 

• In Remote Power Off (RPO) Mode:   

• RPO function is enabled when a jumper feeding the coil of the Remote Power Off relay is removed and 
replaced with wiring to the maintained normally closed (N/C) contacts of a Remote Power Off switch. 
• When the RPO switch is activated input power feeding the isolation transformer is disconnected by the relay 
on both the Line and Neutral conductors which removes power from the IG receptacles and equipment 
• When the RPO switch is deactivated input power feeding the isolation transformer is reconnected by the 
relay which restores power to the IG receptacles and equipment 
 

 
 
 

Summary of Contents for MVP-2KL

Page 1: ...acles along with plug and receptacle connectivity for the Uninterruptible Power Supply UPS The mission of Mac Victor is to Expand Your Power by enhancing the return on investment of your Critical Elec...

Page 2: ...ts 4 2 Location 4 3 Typical Elevation 4 4 Mounting Instructions 4 5 Wiring Diagram Mac Victor 2 0 4 6 Wiring Diagram Remote Power Off 4 7 Wiring Diagram Remote signaling of Input and Output power stat...

Page 3: ...isconnect Switch may be required to de energize the equipment before servicing Service is to be performed by qualified personnel only See Installation Instructions before connecting to the supply The...

Page 4: ...he UPS outlets Do not plug other equipment into the other UPS outlets except for the Mac Victor 2 0 plug assembly Equipment plugged into the other UPS outlets will not function in the bypass mode and...

Page 5: ...acles by injecting electrical noise onto the IG conductor The National Electrical Code NEC allows for an alternative IG grounding method through the use of a separately derived system such as an isola...

Page 6: ...r off relay to the Isolation Transformer with neutral to ground bond Output Surge filter board assembly provides additional surge power protection and noise filtering Output Surge filter board assembl...

Page 7: ...S IG Base Item Number Description MVP 2KS 2kVA Mac Victor 2 0 w straight blade UPS connectors NEMA 5 20P 5 20R MVP 2KL 2kVA Mac Victor 2 0 w locking blade UPS connectors NEMA L5 20P L5 20R MVP 3KL 3kV...

Page 8: ...rical Code NEC NFPA 70 IG Suffix Isolated Ground receptacle option Integrated Isolated Ground Receptacles Option IG suffix includes 4 outlets and a 5th output circuit breaker The Integrated Isolated G...

Page 9: ...closet telecom equipment wall datacom room or other secure locations that are not accessible to the public To minimize the distance of branch circuit runs to the remote Isolated Ground receptacles ch...

Page 10: ...drivers etc Installation Steps Wood Stud Mounting 1 Locate 2 adjacent wooden studs 16 on center at the desired installation location 2 BE SURE TO ACCOUNT FOR THE HEIGHT OF THE UPS TO BE INSTALLED ON T...

Page 11: ...iring must be run in separate conduit from all output wiring All output wiring must be run in dedicated conduits or MC cable and not routed with any other equipment wiring to avoid induced voltages Re...

Page 12: ...ower status pilot lights or to provide dry contact status signals to the inputs of Building Automation Systems Input Power Terminals TS 1 Remote Power Off Relay R1 Remote Power Off Switch maintained N...

Page 13: ...on AHJ and only in gasoline fueling applications These special applications can have fueling data boxes plugged into the IG outlets that may need to be shut down during fueling emergencies This option...

Page 14: ...and latch the front hinged enclosure cover 5 Turn on the input power circuit breaker MB 1 located at the lower front right of the enclosure 6 The Input Power pilot should come on 7 Set the UPS Bypass...

Page 15: ...2 0 Shelf with the front of the UPS facing to the left outlets and power cord facing the right 4 The UPS should be located on the shelf in a position that insures adequate rear ventilation of the UPS...

Page 16: ...ecure any excess cabling 6 Insert the Safety Outlet Protector Plugs included on all open outlets on the back of the UPS 7 Follow the UPS power up procedures as outlined in the accompanying UPS Manual...

Page 17: ...F1 on the Output Surge Filter Board Assembly Standard Surge Monitor Operation POWER ON green LED is ON during normal operation SERVICE red LED is OFF during normal operation SERVICE red LED is ON ind...

Page 18: ...ing up UPS switch back to Normal When the Switch is in Bypass if there is a utility power outage the output power will go off LOSS OF INPUT POWER Input light is OFF and Output light is ON Indication o...

Page 19: ...nd then switch back to the On position If a circuit breaker continues to open check for a circuit overload or a wiring fault A qualified electrician may be required to safely diagnose this problem Sur...

Page 20: ...See Section 6 1 Input circuit breaker trips Overloaded system Remove excess load reset breaker See Section 6 3 UPS output circuit breaker trips Overloaded system Remove excess load reset breaker See...

Page 21: ...fast acting 1 10 amp THOR 0603 0100 02 Mac Victor 2 0 Output SPD Filter Board Assy Located at the bottom of the enclosure TB 1 Relay Output Power TB 2 Relay Input Power Fuse F 2 Fuse F 3 Fuse F 1 Outp...

Page 22: ...al Electrical Code U S Patent Pending Product Features Plug receptacle connectivity to many Uninterruptible Power Supply UPS vendors UPS battery bypass switch normal bypass Make before Break type Prov...

Page 23: ...LLC 10500 Wakeman Drive Suite 105 Fredericksburg VA 22407 Phone 540 220 8116 Fax 540 242 7004 www MacVictor com Mac Victor and Expand Your Power are registered U S trademarks of Mac Victor Power LLC M...