Industrial HMI Touch Panel Hardware Manual
M2I Corporation
11-35, Simin-daero 327beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do 14055, Korea, Tel: +82-70-465-3366, Fax: +82-31-465-3355, www.m2i.co.kr
10 / 22
5.1.4 COM2 Connector pin number and Signal name
Type
Pin No.
Signal
Direction
Meaning
9Pin Female
1
RDA(RD+)
Input
RS-422/485 Receive Data (+)
2
RD(RxD)
Input
RS-232C Receive Data
3
SD(TxD)
Output
RS-232C Send Data
4
RDB(RD-)
Input
RS-422/485 Receive Data (-)
5
SG
-
Signal Ground
6
SDA(SD+)
Output
RS-422/485 Send Data (+)
7
NC
-
Not Available
8
NC
-
Not Available
9
SDB(SD-)
Output
RS-422/485 Send Data (-)
* Be sure to connect the RD and SD to the RS-232C communication line by crossing each other with a Twisted Pair Cable.
Please connect SG directly.
* SG must be connected directly.
*
RS-422/485 communication line must use RDA and RDB as Twisted Pair Cable, SDA and SDB as Twisted Pair
Cable
.
*
Do not use shield wire of communication line as signal ground. It may cause communication failure
.
5.2 Ethernet Communication Specifications
5.2.1 Ethernet
Items
Contents
Ethernet Method
IEEE802.3i/IEEE802.3u, 10BaseT / 100BaseT
Speed
10M / 100Mbps
Communication Method
Base Band
Switching Method
AUTO MDIX
Maximum Segment Length
100M (Hub between products)
Communication Cable
UTP (Unshielded Twisted Pair)
Modular Jack
RJ45
5.2.2 RJ–45 Pin Layout
Type
Pin No.
Color
Signal
1
Orange/White
TD+
2
Orange
TD-
3
Green/White
RD+
4
Blue
Not Available in 10BaseT
5
Blue/White
Not Available in 10BaseT
6
Green
RD-
7
Brown/White
Not Available in 10BaseT
8
Brown
Not Available in 10BaseT
* When HUB is using, Straight cable should be used.
Ex) Straight Cable Wiring: Connect 1:1 according to the wiring diagram above.
* In case of do not using HUB, do not use HUB, when it is connected directly, Cross Cable should be used.
Ex) Cross Cable Wiring: In the above wiring diagram, TD+ and RD+ are changed, and TD- and RD- are exchanged.