background image

R7HL-DC16B

EM-7812-H  Rev.4  P. 2 / 5

COMPONENT IDENTIFICATION

X10

X1

STATION ADD.

1

2

3

4

5

6

7

8

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

4

5

6

7

1

2

3

TERM

ON

OFF

RUN

PWR

ON

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

■ 

FRONT VIEW

■ 

SIDE VIEW

012

34

56

789AB

C

D

EF

012

34

56

789AB

C

D

EF

Terminating Resistor SW

Output Terminals

Network, Power Supply

Terminals

Status Indicator LED

Station Address Setting Rotary SW

Operating Mode Setting DIP SW (SW1)

Discrete Output

Status Indicator LED

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

PWR

Green

Turns on when the internal 5V is sup-
plied normally.

RUN

Green

Turns on when the refresh data is re-
ceived normally. 

 

DISCRETE OUTPUT STATUS INDICATOR LED

LED indicators shows the signal status.

ON   : LED ON (red)
OFF : LED OFF

 

STATION ADDRESS

The left switch determines the sixteenths place digit, while
the right switch does the ones place digit of the address.
(Range: 01H to 3FH)

Station Address Setting (x1)

Station  Address Setting (x16)

012

34

56

789AB

C

D

EF

012

34

56

789AB

C

D

EF

 

OPERATING MODE

(*) Factory setting

• Output at the loss of communication (SW1-7)

SW1-7

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Hold the output (*)
(maintains the last data received normally) 

ON

Reset the output (turned off) 

• Transfer rate (SW1-8)

SW1-8

TRANSFER RATE

OFF

12 Mbps (*)

ON

6 Mbps

Note: Be sure to set unused SW1-1 through 1-6 to OFF.

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and
OFF to invalidate.  (Factory setting OFF)

 

NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT

• Full-duplex communication

4

RXD+

5

6

7

1

2

3

RXD– +24V 0V

TXD+ TXD– FG

NO.

ID

FUNCTION, NOTES

1

TXD+

Network (slave, transm)

2

TXD–

Network (slave, transmission –)

3

FG

FG

4

RXD+

Network (master, transm)

5

RXD–

Network (master, transmission –)

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

• Half-duplex communication

4

TR

+

5

6

7

1

2

3

TR

– +

24V

0V

NC

NC

FG

NO.

ID

FUNCTION, NOTES

1

NC

No connection

2

NC

No connection

3

FG

FG

4

TR+

Network

5

TR–

Network

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7HL-DC16B-R

Page 1: ...n regard to the whole system and employ additional protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 45mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and output signal for safety DO NOT set ...

Page 2: ...s Setting x1 Station Address Setting x16 0 1 2 3 4 5 6 789A B C D E F 0 1 2 3 4 5 6 789A B C D E F OPERATING MODE Factory setting Output at the loss of communication SW1 7 SW1 7 OUTPUT AT THE LOSS OF COMMUNICATION OFF Hold the output maintains the last data received normally ON Reset the output turned off Transfer rate SW1 8 SW1 8 TRANSFER RATE OFF 12 Mbps ON 6 Mbps Note Be sure to set unused SW1 ...

Page 3: ...14 Y7 Output 7 6 Y8 Output 8 15 Y9 Output 9 7 YA Output 10 16 YB Output 11 8 YC Output 12 17 YD Output 13 9 YE Output 14 18 YF Output 15 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 4 5 6 7 1 2 3 10 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 DIN RAIL 35mm wide 54 2 13 17 66 115 4 53 5 20 30 1 18 3 12 5 5 22 50 1 97 18 5 73 7 M3 SCREW TERMINALS for N...

Page 4: ...is NOT a protective conductor terminal WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Recommended solderless terminal Communication cables Applicable wire size 0 2 to 0 5 mm2 AWG 26 to 22 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Others Applicable wir...

Page 5: ...odule TR TR FG SHIELD Slave Module TR TR SHIELD Note Be sure to turn ON the switch of the terminating resistor located at both ends of the modules Terminating Resistor Terminating Resistor MASTER CONNECTION Full duplex communication Half duplex communication I O DATA DESCRIPTIONS DISCRETE OUTPUT Unused 0 15 0 15 Di Do Output 0 Output 1 Output 2 Output 3 Output 15 Output 7 Output 8 0 OFF 1 ON 056 2...