R7HL-DC16B

EM-7812-H  Rev.4  P. 4 / 5

 

CONNECTION DIAGRAM

■ 

Output Connection Example

4

7

6

3

2

1

5

0V

24V DC

FG

TXD– (NC)

TXD+ (NC)

RXD– (TR–)

RXD+ (TR+)

10

17

18

1

YD

16

YB

0V

YF

15

Y9

14

Y7

13

Y5

12

Y3

11

Y1

9

YE

8

YC

7

YA

6

Y8

5

Y6

4

Y4

3

Y2

+24V

Y0

2

10

1

2

Y0

0V

+24V

+

18

YF

Note 1: Terminal numbers

 in parentheses are for half-duplex communication model.

Note 2: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.5 N·m 

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.

Recommended solderless terminal:

• Communication cables

  Applicable wire size: 0.2 to 0.5 mm

2

 (AWG 26 to 22)

  Recommended manufacturer: Japan Solderless Terminal 

MFG. Co., Ltd.

• Others

  Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16) 

  Recommended manufacturer: Japan Solderless Terminal 

MFG. Co., Ltd. or Nichifu Co., Ltd.

4 (.16) min

3.2 (.13) dia. 

mm (inch)

6 (.24) max

3.3 (.13) max

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7HL-DC16B-R

Page 1: ...n regard to the whole system and employ additional protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 45mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and output signal for safety DO NOT set ...

Page 2: ...s Setting x1 Station Address Setting x16 0 1 2 3 4 5 6 789A B C D E F 0 1 2 3 4 5 6 789A B C D E F OPERATING MODE Factory setting Output at the loss of communication SW1 7 SW1 7 OUTPUT AT THE LOSS OF COMMUNICATION OFF Hold the output maintains the last data received normally ON Reset the output turned off Transfer rate SW1 8 SW1 8 TRANSFER RATE OFF 12 Mbps ON 6 Mbps Note Be sure to set unused SW1 ...

Page 3: ...14 Y7 Output 7 6 Y8 Output 8 15 Y9 Output 9 7 YA Output 10 16 YB Output 11 8 YC Output 12 17 YD Output 13 9 YE Output 14 18 YF Output 15 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 4 5 6 7 1 2 3 10 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 DIN RAIL 35mm wide 54 2 13 17 66 115 4 53 5 20 30 1 18 3 12 5 5 22 50 1 97 18 5 73 7 M3 SCREW TERMINALS for N...

Page 4: ...is NOT a protective conductor terminal WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Recommended solderless terminal Communication cables Applicable wire size 0 2 to 0 5 mm2 AWG 26 to 22 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Others Applicable wir...

Page 5: ...odule TR TR FG SHIELD Slave Module TR TR SHIELD Note Be sure to turn ON the switch of the terminating resistor located at both ends of the modules Terminating Resistor Terminating Resistor MASTER CONNECTION Full duplex communication Half duplex communication I O DATA DESCRIPTIONS DISCRETE OUTPUT Unused 0 15 0 15 Di Do Output 0 Output 1 Output 2 Output 3 Output 15 Output 7 Output 8 0 OFF 1 ON 056 2...

Reviews: