background image

R7D-SV4

EM-7802-A  Rev.7  P. 6 / 10

 

STATUS

Bit 0 to 7:  Analog input module can show input status of each channel.
Bit 8 to 10:  Shows the power supply status.

0

15

Input 0 (Input range error)
Input 1 (Input range error)
Input 2 (Input range error)

Unused

Input 3 (Input range error)
Input 0 (ADC error)
Input 1 (ADC error)
Input 2 (ADC error)
Input 3 (ADC error)

     :

     :

     :

Network power supply
Unused

Unused

Extension module external power supply

Input range error (≤ -15%, ≥ 115%)
     0 : Normal     1 : Error
ADC error (no response from ADC)
     0 : Normal     1 : Error
Power supply
     0 : Normal     1 : Error

TRANSMISSION DATA DESCRIPTIONS

 

BASIC MODULE

Transmitted data (word) depends upon the modules types.

MODEL

OUTPUT DATA

*

1

INPUT DATA

*

2

(R7D to Master)

(Master to R7D)

R7D-SV4

4

0

 

EXTENSION MODULE

Transmitted data (word) for the extension module is added.

MODEL

OUTPUT DATA

*

1

INPUT DATA

*

2

(R7D to Master)

(Master to R7D)

R7D-EAx

1

0

R7D-ECx

0

1

 

STATUS

Status signal can be included in the transmission data 
when the setting is enabled using the PC Configurator soft-
ware (model: R7CON).  For details, refer to “STATUS in I/O 
DATA DESCRIPTIONS”.

STATUS

OUTPUT DATA

*

1

INPUT DATA

*

2

(R7D to Master)

(Master to R7D)

Enabled

1

0

Disabled

0

0

*1. Output Data means those sent to the master.
*2. Input Data means those received from the master.

WIRING INSTRUCTIONS

 

SCREW TERMINAL (Input)

Torque: 0.5 N·m

• SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

 

EURO TYPE CONNECTOR TERMINAL (DeviceNet)

Applicable wire size: 0.2 – 2.5 mm

2

Stripped length: 7 mm

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7D-SV4/UL

Page 1: ...titude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be...

Page 2: ...bps 1 250 kbps or 2 500 kbps For the settings 3 through 9 it analyzes the PLC s network to determine the baud rate on the network OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSI...

Page 3: ...ETTING Communication Timeout 0 0 3276 7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID English one byte characters within 8 characters CHANNEL INDIVIDUAL SETTING PARAMETER SETTING...

Page 4: ...PUT 6 24 TERMINAL BLOCK for DeviceNet POWER CONNECTION DIAGRAM 1 VH0 10 VL0 11 I0 2 COM0 INPUT 0 3 VH1 12 VL1 13 I1 4 COM1 INPUT 1 6 VH2 15 VL2 16 I2 7 COM2 INPUT 2 8 VH3 17 VL3 18 I3 9 COM3 INPUT 3 I...

Page 5: ...put Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Input Module without Status Example 2 Analog Input Module R7D EC16x with Status R7D EC16x Input D...

Page 6: ...is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D ECx 0 1 STATUS Status signal can be included in the transmission data when the setting is enabled using the PC Co...

Page 7: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7D module...

Page 8: ...d the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Page 9: ...cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact...

Page 10: ...pplicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it...