R3-NL1

P. 2 / 8

EM-8427 Rev.5

COMPONENT IDENTIFICATION

SIDE DIP SW

Data Allocation

: SW1, SW2

Data Allocation Type* must be assigned to each I/O
module position to specify how many data areas (four
types) are to be occupied by each.
Two bits from SW1 and SW2 are assigned to each position,
and data areas can be specified from the module No. 1
through 8.  Setting for No. 9 and later modules is identical
to No. 8.

SW3-4

LED

RUN

ERR

OFF (*)

Green when normal

Green when abnormal

ON

Red when receiving

Red when transmitting

(*) Factory setting

SW ASSIGNMENT

MODULE NO.

SW1-1

SW1-2

1

SW1-3

SW1-4

2

SW1-5

SW1-6

3

SW1-7

SW1-8

4

SW2-1

SW2-2

5

SW2-3

SW2-4

6

SW2-5

SW2-6

7

SW2-7

SW2-8

8

SW SETTTING

DATA ALLOCATION

OFF

OFF

1

ON

OFF

4

OFF

ON

8

ON

ON

16

SW

DUAL COMMUNICATION

MAIN

 (*)

SUB

SW3-1

OFF

ON

SW

INPUT ERROR DATA

HOLD 

(*)

SET ‘0’

SW3-2

OFF

ON

RUN LED

FRONT VIEW

SIDE VIEW

ERR LED

1

2

3

4

5

6

Terminal Block

ONLINE LED

SERVICE SW

SERVICE LED

RESET SW

Configuration Jack

1
2
3
4
5

SW2

ON

8
7
6
5
4
3
2
1

SW3

ON

4
3
2
1

ON

8
7
6
5
4
3
2
1

SW1

Functions & Data Allocation

Setting

Dual Communication

: SW3

When two network modules are mounted, one must be
‘Main’ (OFF) network and the other must be ‘Sub’ (ON)
network.  For single communication, the network module
must always be set to ‘Main’ (OFF).

Input Error Data

: SW3

Hold

: When the communication from an input module is lost

due to the input module error, the network module holds the
signal and stands by until the communication recovers.

Set to ‘0’

: When the communication from an input module is

lost due to the input module error, the network module out-
puts ‘0.’

LED Function

: SW3

Functions assigned to the front RUN and ERR LEDs can
be selected.

ONLINE & SERVICE INDICATOR LED

ONLINE indicator

: Red LED

ON

:

Off-line or no network information (de-
commissioned)

Flashing in approx. 0.5 Hz

: On-line (ready to communi-

cate network variables)

Flashing in approx. 5 Hz for 30 sec

: Wink message

received

SERVICE indicator

: Green LED

OFF

:

Normal operations

Flashing in approx. 0.5 Hz

: No network information

ON

:

Internal program error

*Refer to the specifications of the related series for the
Data Allocation Type of I/O modules.

Summary of Contents for R3-NL1

Page 1: ...nvironmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 30 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct AND The u...

Page 2: ...W2 ON 8 7 6 5 4 3 2 1 SW3 ON 4 3 2 1 ON 8 7 6 5 4 3 2 1 SW1 Functions Data Allocation Setting Dual Communication SW3 When two network modules are mounted one must be Main OFF network and the other must be Sub ON network For single communication the network module must always be set to Main OFF Input Error Data SW3 Hold When the communication from an input module is lost due to the input module err...

Page 3: ...ess terminals with insulation sleeve do not fit Applicable wire size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE TERMINAL COVER 6 M3 SCREW 6 2 24 COMMUNICATION CABLE CONNECTIONS INTERNAL POWER INTERNAL COMM BUS CONFIGURATION JACK JACK BUS CONNECTOR Not provided with No Power Supply type module 1 4 RUN RUN RUN CONTACT OUTPU...

Page 4: ... NVO 5 nvoCardErr SNVT_state Each module s error status Each module status cpMaxSendTime cpMinSendTime SCPTmaxSendTime SCPTminSendTime Input data sending intervals Input data minimum sending intervals Configuration Properties ANALOG INPUT OUTPUT NO of DATA DEVICE IMAGE USABLE FUNCTIONAL BLOCKS INPUT OUTPUT APB FILE 16 0 R3NL1_1_101 APB NodeObjet GetValue 0 15 Can be defined from 0 to 15 12 4 R3NL1...

Page 5: ...nvoVal Value deviation to be sent SCPTnvType Network variable type etc Configuration Properties ANALOG OUTPUT FUNCTIONAL BLOCKS SetValue 0 through 15 SetValue X cpNviDefValue cpNviMaxRnge cpNviMinRnge cpNviType identical to nviVal identical to nviVal Default value at the startup Span full scale value identical to nviVal Zero value SCPTnvType Network variable type etc Configuration Properties nviVa...

Page 6: ... 65535 0 nvoCardStatus SNVT_state Indicates that I O modules are mounted in each slot 0 or 1 Bit 0 through bit 15 are applied for slot 1 through 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Not mounted 1 Mounted nvoCardErr SNVT_state Indicates error status for each module slot 0 or 1 Bit 0 through bit 15 are applied for slot 1 through 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Normal 1 Error CONFIGURATION TYPE ...

Page 7: ... Default nvoVal SNVT_lev_percent Data acquired from assigned channels 163 85 through 163 830 Set SNVT_lev_percent for the input types other than 0 0 discrete or temperature Change the network variable type according to the input type if necessary ConfigurationProperty value must be re read after the network variable type is changed Use ResyncCP on the LonMaker SNVT_state For descrete inputs change...

Page 8: ...lowed by Output or SetValue R3Do The 1st output must be the 1st transmitted data in the slot next to the one with the last input data Example 1 Data Area Module 1 4 GetValue 0 3 Module 2 4 GetValue 4 7 Module 3 4 SetValue 0 Module 4 1 SetValue 1 Module 5 1 SetValue 2 Module 6 1 SetValue 3 Module 7 1 SetValue 4 Module 8 1 SetValue 5 Module 9 1 SetValue 6 Module 10 1 SetValue 7 Example 2 Data Area M...

Reviews: