I/O DATA DESCRIPTIONS 

 MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

Shows each module’s availability and error status.

 ANALOG DATA (models: R3-SV4, YV4, DS4, YS4 and US4)

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).  Negative percentage is represented in 
2’s complements.

 TEMPERATURE DATA (models: R3-RS4, TS4 and US4)

16-bit binary data.
With °C  temperature unit, raw data is multiplied by 10.  For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.  For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.

 16-POINT DISCRETE DATA (models: R3-DA16 and DC16)

0

15

Module 1
Module 2
Module 3

      :
Module 16

0

15

0

15

0

15

Input 1   (Output 1)
Input 2   (Output 2)
Input 3   (Output 3)

     :               :
Input 16 (Output 16)

0 : OFF (open)

1 : ON (close)

Summary of Contents for R3-NC2

Page 1: ...metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the uni...

Page 2: ...SW2 ON 8 7 6 5 4 3 2 1 SW3 ON 4 3 2 1 ON 8 7 6 5 4 3 2 1 SW1 Functions 1 2 3 4 5 6 Terminal Block Configuration Jack 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 FG SLD DG DB DA Node A...

Page 3: ...re size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max COMMUNICATON CABLE CONNECTIONS DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG R3 NC2 DA DB DG SLD FG I O UNIT TERMINATOR blue white y...

Page 4: ...ATA The figure below shows the allocation of the data sent from the network module to the master INPUT DATA The figure below shows the allocation of the data sent from the master to the network module...

Page 5: ...US4 out of 10 to 110 the other types out of 15 to 115 sta tus for each module The bit corresponding to such modules turns to 1 RX n 3 through RX n 6 are unused RX n 8 through RX n 14 are unused RX n 7...

Page 6: ...TA models R3 RS4 TS4 and US4 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is...

Page 7: ...L INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER M System Co Ltd 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 06 6659 8201 Fax 06 6659 8510 E mail info m system co jp PARAMETERS...

Reviews: