R3-NC2

P. 4 / 7

EM-842 Rev.8

TRANSMISSION DATA DESCRIPTIONS

The DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
     

Module 1 

 

4

     

Module 2 

 

4

     

Module 3 

 

4

     

Module 4 

 

4

     

Module 5 

 

4

     

Module 6 

 

1

     

Module 7 

 

1

     

Module 8 

 

1

Then the I/O data are assigned as in the figures below:

 OUTPUT DATA 

The figure below shows the allocation of the data sent from 
the network module to the master.

 INPUT DATA 

The figure below shows the allocation of the data sent from 
the master to the network module.

Thirty-two (32) data areas are available to the R3-NC2.  Total data areas occupied by I/O modules must be within this limi-
tation.

0

15

 RWr n+0

+2

+4

+6

+8

+10

+12

+14

Module 1

Module 2

Module 3

+16

+18

Module 6

+20

Module 7
Module 8

+22

+30

Module 4

Module 5

Unused

0

15

 RWw n+0

+2

+4

+6

+8

+10

+12

+14

Module 1

Module 2

Module 3

+16

+18

Module 6

+20

Module 7
Module 8

+22

+30

Module 4

Module 5

Unused

Summary of Contents for R3-NC2

Page 1: ...metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the uni...

Page 2: ...SW2 ON 8 7 6 5 4 3 2 1 SW3 ON 4 3 2 1 ON 8 7 6 5 4 3 2 1 SW1 Functions 1 2 3 4 5 6 Terminal Block Configuration Jack 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 FG SLD DG DB DA Node A...

Page 3: ...re size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max COMMUNICATON CABLE CONNECTIONS DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG R3 NC2 DA DB DG SLD FG I O UNIT TERMINATOR blue white y...

Page 4: ...ATA The figure below shows the allocation of the data sent from the network module to the master INPUT DATA The figure below shows the allocation of the data sent from the master to the network module...

Page 5: ...US4 out of 10 to 110 the other types out of 15 to 115 sta tus for each module The bit corresponding to such modules turns to 1 RX n 3 through RX n 6 are unused RX n 8 through RX n 14 are unused RX n 7...

Page 6: ...TA models R3 RS4 TS4 and US4 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is...

Page 7: ...L INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER M System Co Ltd 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 06 6659 8201 Fax 06 6659 8510 E mail info m system co jp PARAMETERS...

Reviews: