R3-NC2

P. 2 / 7

EM-842 Rev.8

COMPONENT IDENTIFICATION

 BAUD RATE ROTARY SW 

SW POSITION

BAUD RATE

0

156 kbps

1

625 kbps

2

2.5 Mbps

3

5 Mbps

4

10 Mbps

Other

Unused.  ERR LED turns on if used.

 SIDE DIP SW

• Data Allocation

: SW1, SW2

Data Allocation Type* must be assigned to each I/O mod-
ule position to specify how many data areas (four types) 
are to be occupied by each.
Two bits from SW1 and SW2 are assigned to each posi-
tion, and data areas can be specified from the module No. 1 
through 8.  Setting for No. 9 and later modules is identical 
to No. 8.

SW ASSIGNMENT

MODULE NO.

SW1-1

SW1-2

1

SW1-3

SW1-4

2

SW1-5

SW1-6

3

SW1-7

SW1-8

4

SW2-1

SW2-2

5

SW2-3

SW2-4

6

SW2-5

SW2-6

7

SW2-7

SW2-8

8

SW SETTTING

DATA ALLOCATION

OFF

OFF

1

ON

OFF

4

OFF

ON

8

ON

ON

16

*Refer to the specifications of the related series for the 
Data Allocation Type of I/O modules.

RUN LED

■ 

FRONT VIEW

■ 

SIDE VIEW

ERR LED

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

ON

8

7

6

5

4

3

2

1

SW1

Functions

1
2
3

4
5
6

Terminal Block

Configuration Jack

5

4 3 2 1

0

9

8

7

6

5

4 3 2 1

0

9

8

7

6

5

4 3 2 1

0

9

8

7

6

FG

SLD

DG

DB

DA

Node Address

Rotary SW

Baud Rate

Rotary SW

SA1

x10

SA2

x1

B RATE

• Dual Communication

: SW3

When two network modules are mounted, one must be  
‘Main’ (OFF) network and the other must be  ‘Sub’ (ON) 
network.  For single communication, the network module 
must always be set to  ‘Main’ (OFF). 

SW

DUAL COMMUNICATION

MAIN (

*

)

SUB

SW3-1

OFF

ON

• Input Error Data

: SW3

Hold:

 When the communication from an input module is 

lost due to the input module error, the network module 
holds the signal and stands by until the communication 
recovers.

Set to ‘0’:

 When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD (

*

)

SET 

 ‘0’

SW3-2

OFF

ON

• LED Function

: SW3

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED

RUN

ERR

OFF (*)

Green when normal

Green when abnormal

ON

Red when receiving

Red when transmitting

(*) Factory setting

Summary of Contents for R3-NC2

Page 1: ...metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the uni...

Page 2: ...SW2 ON 8 7 6 5 4 3 2 1 SW3 ON 4 3 2 1 ON 8 7 6 5 4 3 2 1 SW1 Functions 1 2 3 4 5 6 Terminal Block Configuration Jack 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 FG SLD DG DB DA Node A...

Page 3: ...re size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max COMMUNICATON CABLE CONNECTIONS DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG R3 NC2 DA DB DG SLD FG I O UNIT TERMINATOR blue white y...

Page 4: ...ATA The figure below shows the allocation of the data sent from the network module to the master INPUT DATA The figure below shows the allocation of the data sent from the master to the network module...

Page 5: ...US4 out of 10 to 110 the other types out of 15 to 115 sta tus for each module The bit corresponding to such modules turns to 1 RX n 3 through RX n 6 are unused RX n 8 through RX n 14 are unused RX n 7...

Page 6: ...TA models R3 RS4 TS4 and US4 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is...

Page 7: ...L INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER M System Co Ltd 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 06 6659 8201 Fax 06 6659 8510 E mail info m system co jp PARAMETERS...

Reviews: