P.  / 4

EM-5657 Rev.7

THERMOCOUPLE & DC INPUT MODULE

(16 points)

MODEL

R1M-GH

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If  you  have  any  problems  or  questions  with  the  product, 
please contact M-System’s Sales Office or representatives.

This product is for use in general industrial environments, 
therefore may not be suitable for applications which require 
higher level of safety (e.g. safety or accident prevention sys-
tems) or of reliability (e.g. vehicle control or combustion con-
trol systems).

For  safety,  installation  and  maintenance  of  this  product 
must be conducted by qualified personnel.

 PACKAGE INCLUDES:

  Remote I/O module (body + CJC sensor) ..................... (1)

 MODEL NO.

Confirm  Model  No.  marking  on  the  product  to  be  exactly 
what you ordered.

 INSTRUCTION MANUAL

This  manual  describes  necessary  points  of  caution  when 
you use this product, including installation, connection and 
basic maintenance procedures.
For  detailed  information  on  Modbus  supported  functions, 
refer to Modbus Protocol Reference Guide (EM-5650).
The R1M is programmable using the PC configurator soft-
ware.    For  detailed  information  on  the  PC  configuration, 
refer to the R1CON instruction manual.  The R1CON PC 
Configurator Software is downloadable at M-System’s web 
site: http://www.m-system.co.jp.

POINTS OF CAUTION

 CONFORMITY WITH EC DIRECTIVES

• This equipment is suitable for use in a Pollution Degree 

2 environment and in Installation Category II, with the 
maximum operating voltage 300V.

  Basic insulation is maintained between the signal input 

and RS-232C/RS-485.  Prior to installation, check that the 
insulation class of this unit satisfies the system require-
ments.

• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• Insert noise filters.  Okaya Electric Industries Model SUP-

E1H or equivalent for the power source connected to the 
unit,  and TDK  Model  ZCAT3035-1330  or  equivalent  for 
the RS-232C cable are recommended.

• The  equipment  must  be  installed  such  that  appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.

• The actual installation environments such as panel con-

figurations,  connected  devices,  connected  wires,  may  af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 10VA
  24V DC rating: 24V ±10%, approx. 7W
 

 GENERAL PRECAUTIONS

• Before you remove the module, turn off the power supply 

and input signal for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install  the  module  inside  proper  housing  with  sufficient 
ventilation.

• Do not install the module where it is subjected to continu-

ous vibration.  Do not apply physical impact to the mod-
ule.

• Environmental temperature must be within -5 to +60°C     

(23 to 140°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 WIRING

• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tight-

ly.

• Do  not  install  cables  (power  supply,  input  and  output) 

close  to  noise  sources  (relay  drive  cable,  high  frequency 
line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

• The  module  is  designed  to  function  as  soon  as  power  is 

supplied, however, a warm up for 10 minutes is required 
for satisfying complete performance described in the data 
sheet.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for R1M Series

Page 1: ...rotocol Modbus RTU Protocol Modbus RTU Refer to Modbus Protocol Reference Guide EM 5650 for supported functions RS 232 C Standard Conforms to RS 232 C EIA Transmission distance 10 meters max RS 485 St...

Page 2: ...700 C or 1292 F The described accuracy may be partially not satisfied when the temperature ranges below 0 C STANDARDS APPROVALS CE conformity EMC Directive 2004 108 EC EMI EN 61000 6 4 2007 EMS EN 61...

Page 3: ...e When the device is not at the end remove the jumper pin Remark 1 This device is not designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables...

Page 4: ...slave 04 Read Input Registers X Collected data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave...

Page 5: ...17 48 F Reserved for AO in engineering unit 145 160 Y Y I I O type No 161 176 Y I Burnout type 161 168 for Type J3 0 No burnout 1 Upscale 2 Downscale 4 I 16 bit integer F 32 bit floating B16 16 byte...

Page 6: ...E A D DATA Decimal DC 20V 20000 5V 5000 1V 10000 0 8V 8000 0 2V 20000 50mV 5000 10mV 10000 Thermocouple Temperature x 10 RTD Temperature x 10 Potentiometer 0 100 2000 0 500 0 1k 0 10k BIT NAME DESCRIP...

Page 7: ...00 to 600 C 0X1B L 200 to 900 C 0X1C P Platinel II 0 to 1395 C R1M J3 RTD input 0X30 JPt 100 JIS 89 200 to 500 C 0X31 Pt 100 JIS 89 200 to 660 C 0X32 Pt 100 JIS 97 IEC 200 to 850 C 0X33 Pt 50 JIS 81 2...

Page 8: ...istance between the PC and the R1Ms is long insert an RS 232 C RS 485 Converter for isolation RS 232 C RS 232 C RS 485 Converter model R2K 1 Specifications are subject to change without notice Ruggh l...

Page 9: ...urce connected to the unit and TDK Model ZCAT3035 1330 or equivalent for the RS 232C cable are recommended The equipment must be installed such that appropriate clearance and creepage distances are ma...

Page 10: ...5 T1 T2 T3 T4 T5 T6 T7 CJC Sensor model CJM RS 485 Connector Address Setting Rotary SW Configurator Jack Specifications Marking Power Terminals RS 232C 9 pin Connector RUN Indicator LED DIN Rail Adapt...

Page 11: ...t the end remove the jumper pin Remark 1 This device is not designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables Remark 2 Be sure to maint...

Page 12: ...alibration procedure is explained below CALIBRATION Warm up the unit for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the output signal for the respective input signal remains...