TROUBLESHOOTING

TROUBLE

POWER

LED

INPUT

LED

STATUS

LED

POSSIBLE CAUSE

HOW TO PROCEED

Actuator 
does not 
work

ON

ON

Blink

2 sec. 

intervals

Abnormal input signal.
(No change over deadband)

Check input signal.
Narrow the deadband.

ON

---- *

Blink

0.5 sec.

intervals

Actuator mechanism is damaged.

Repair the unit.

Overload caused by a foreign object caught 
in the valve.

Check the valve.

Control PCB damaged.

Repair or replace the PCB.

Wiring error at the motor or position sensor. Check the connector.
Low power voltage or insufficient power 
supply.

Check the power supply.

ON

OFF

Blink
2 sec.

intervals

Abnormal input signal.

Check the input signal.

Wiring error at the input signal.

Check the connector and connecting section.

OFF

---- *

---- *

Wiring error at the power supply.

Check the connector and connecting section.

Abnormal power voltage.

Check the power supply.

Fuse melted.

Replace the fuse.

ON

---- *

ON

Malfunction by noise.

Turn off the power supply and restart.

Low power voltage or insufficient power 
supply.

Check the power supply.

ON

---- *

OFF

Malfunction by noise.

Turn off the power supply and restart.

Low power voltage or insufficient power 
supply.

Check the power supply.

Unstable operation

Power voltage is low or fluctuating.

Check the power supply.

Unstable input signal.

Check the controller, cables.  Eliminate 
noise.

Position sensor (potentiometer) damaged.

Replace the potentiometer.

Stem stops in the middle of stroke 
or
Stem slows down in the middle of 
stroke

Actuator mechanism is damaged.

Repair the unit.

Overload caused by a foreign object caught 
in the valve.

Check the valve.

* The input LED status does not matter.

For repair or parts replacement, consult M-System or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protec-
tors for protection against induced lightning surges. 

 

 

Please consult M-System for appropriate models.

Summary of Contents for MSP4

Page 1: ...264V 47 66 Hz approx 25VA 24V AC rating 24V AC 10 47 66 Hz approx 25VA MSP6 24V DC 24V rating 10 approx 0 6A Built in power fuse 250V 1A rating time delay A rush current 1 5 times as high as the abov...

Page 2: ...SP stops supplying power to the motor and the status LED blinks at 0 5 sec intervals The protection can be reset by applying an input signal to move the output stem in the opposite direction or turnin...

Page 3: ...Packing Figure 2 1 MSP6 Component Identification OFF 1 2 3 4 ON PWR INP ALM DLY ZERO SPAN DZ SW1 Insulation Sheet Fuse Connector ZERO SPAN DZ DLY SW1 PWR INP ALM Zero Adjustment Span Adjustment Deadb...

Page 4: ...10 MSP5 3 50 10 20 MSP6 3 58 10 20 MSP6 4 78 20 40 MANUAL OPERATION FUNCTION for MSP4 MSP5 with AC power supply 1 Be sure to turn OFF the power voltage Operation with power voltage being applied may r...

Page 5: ...ing M Systems s yoke set model YSS for Japan sales only refer to Instruction Manual NM 4893 of the yoke set for the installation procedure MSPx Bolts M5 Position Indicator Yoke Lock Nut Output Stem Va...

Page 6: ...to stop turning as soon as they hit the stoppers ADJUSTMENT PROCEDURE A Zero and Span Supply power voltage to the MSP and apply 0 100 input Turn Zero adjuster to adjust the lower end or fully extended...

Page 7: ...HOW TO PROCEED Stem operation Apply input 0 50 100 then back to 50 0 Check that the actuator operates and positions cor rectly at each input value Repair or calibrate the unit Abnormal sound Check if...

Page 8: ...supply Check the connector and connecting section Abnormal power voltage Check the power supply Fuse melted Replace the fuse ON ON Malfunction by noise Turn off the power supply and restart Low power...