OUTPUT STEM POSITION ADJUSTABILITY

The control PCB compares and amplifies input signal (set-
point) and position feedback signal from the potentiometer, 
and drives the motor to such a direction that the difference 
of the two signals is minimized.

0

25

50

75

100

25

50

75

100

0

INPUT SIGNAL (%)

STEM POSITION (%)

Span Counterclockwise

Zero Clockwise

Zero Counterclockwise

Span Clockwise

Adjustable Zero Range

Adjustable Span Range

Figure 4.  I/O Characteristics (Adjustable Range)

Maximum Stroke

Minimum Stroke

L

Yoke Surface

<Reference 

position>

Figure 5.  Minimum & Maximum Stroke

Table 1.  Available Stroke Range for Each Model

MODEL

L

MIN. STROKE

MAX. STROKE

MSP4-1

29

  5

10

MSP4-2

34

  8

15

MSP5-1

40

  5

10

MSP5-3

50

10

20

MSP6-3

58

10

20

MSP6-4

78

20

40

MANUAL OPERATION FUNCTION

(for MSP4 & MSP5 with AC power supply)

1) Be sure to turn OFF the power voltage. 

Operation with power voltage being applied may result 

in electrical shock or system breakdown. 

2) Remove the screw cap on the top surface of the cover us-

ing a 22- mm wrench, etc.

3) Insert the attached hexagon key wrench in the manual 

drive shaft as shown in the figure below.

4) The wrench turning direction and the stem operation 

direction when seen from above differ according to the 

model as shown in the table below. 

MODEL

NO. OF TURNS
/OPERATION DISTANCE
[turns/mm]

TURNING DIRECTION
/ OPERATION DIRECTION

MSP4-x3
MSP5-x3

  27 / mm 

CCW 
/ GO DOWN

MSP4-x4
MSP5-x4

  54 / mm

CCW
/ GO UP

MSP4-x7
MSP5-x7

112 / mm

CCW
/ GO DOWN

5)  Tighten the cap on the cover with a torque of 4 to 6 N·m.  

Tightening with an excessive torque may damage the 
screw thread of the cap.

Cap

Hexagon key wrench

O ring

Cover

Drive shaft

Figure 6.  Manual Drive Shaft

Note:  The manual operation function is not available for 24V 

DC power model.

Summary of Contents for MSP4

Page 1: ...264V 47 66 Hz approx 25VA 24V AC rating 24V AC 10 47 66 Hz approx 25VA MSP6 24V DC 24V rating 10 approx 0 6A Built in power fuse 250V 1A rating time delay A rush current 1 5 times as high as the abov...

Page 2: ...SP stops supplying power to the motor and the status LED blinks at 0 5 sec intervals The protection can be reset by applying an input signal to move the output stem in the opposite direction or turnin...

Page 3: ...Packing Figure 2 1 MSP6 Component Identification OFF 1 2 3 4 ON PWR INP ALM DLY ZERO SPAN DZ SW1 Insulation Sheet Fuse Connector ZERO SPAN DZ DLY SW1 PWR INP ALM Zero Adjustment Span Adjustment Deadb...

Page 4: ...10 MSP5 3 50 10 20 MSP6 3 58 10 20 MSP6 4 78 20 40 MANUAL OPERATION FUNCTION for MSP4 MSP5 with AC power supply 1 Be sure to turn OFF the power voltage Operation with power voltage being applied may r...

Page 5: ...ing M Systems s yoke set model YSS for Japan sales only refer to Instruction Manual NM 4893 of the yoke set for the installation procedure MSPx Bolts M5 Position Indicator Yoke Lock Nut Output Stem Va...

Page 6: ...to stop turning as soon as they hit the stoppers ADJUSTMENT PROCEDURE A Zero and Span Supply power voltage to the MSP and apply 0 100 input Turn Zero adjuster to adjust the lower end or fully extended...

Page 7: ...HOW TO PROCEED Stem operation Apply input 0 50 100 then back to 50 0 Check that the actuator operates and positions cor rectly at each input value Repair or calibrate the unit Abnormal sound Check if...

Page 8: ...supply Check the connector and connecting section Abnormal power voltage Check the power supply Fuse melted Replace the fuse ON ON Malfunction by noise Turn off the power supply and restart Low power...

Reviews: