MOUNTING REQUIREMENTS  

unit: mm (inch)

54 (2.13)

B

A

120 (4.72)

[Base Socket]

75 (2.95)

[Mounting Block]

4–6 (.24) dia. or M5

A

225 (8.86)

MB-08

428 (16.85)

B

215 (8.46) 418 (16.46)

MB-16

120 (4.72)

[Base Socket]

48 (1.89)

2–4.5 (.18) dia. or M4

75 (2.95)

[Mounting Block]

[29]

(1.14)

■ 

MB-01

26 (1.02) min.

15 (.59)

120 (4.72)

[Base Socket]

48 (1.89)

2–4.5 (.18) dia. or M4

75 (2.95)

[Mounting Block]

[29]

(1.14)

[33]

(1.30)

■ 

MB-P1

■ 

MB-08, MB-16

50 (1.97)

min.

40 (1.57)

[     ] indicates a space required for NPT fitting.

PIPING

Choose an appropriate pipe diameter considering the re-
quired supply pressure to all transducers mounted onto the 
MB.
Connect a stopping valve at the pipe connection to the air 
header for easy testing and maintenance.
Blow the piping before installing the transducers in order to 
remove dust in it.  Use dry air containing no carbon black or 
other foreign particles.  To ensure reliability, use an air filter 
(0.01 microns).  Be sure that no water, oil or dust particles 
enter the transducer by way of supply air.
Tightening torque is at the maximum of 12 N·m.  Check 
that there is no air leak at the connection after sealing it.