Screw attaching
the base to the MB
(included in the transducer)
Screw attaching the body
to the base
(included in the transducer)
Screw attaching the body
to the base
(included in the transducer)
Closing Panel
Base socket
(included in the transducer)
■
MB-08 or MB-16
Base socket
(included in the transducer)
Screw attaching
the base to the MB
(included in the transducer)
Gasket
I/P Transducer Body
(P-UNIT)
I/P Transducer Body
(H-UNIT)
Specifications
Mounting Screw
Mounting Block
INSTALLATION
Secure an appropriate environment before installing the
Mounting Block and I/P Transducer. Refer to ‘Component
Identification’ and ‘Mounting Requirement.’
The Mounting Block, except for the model MB-P1, can be
mounted on the Standard Rack Mounting Frame model BX-
16H which fits into 19-inch rack.
■
MB-01
The MB-01 is designed to be fixed together with the base
socket of the transducer by the same screws. Get the H-
UNIT Series I/P Transducer ready at hand when installing
the MB-01.
1) Remove the closing panel. Be sure to keep the gasket at-
tached to the closing panel so that it will be reused when
attaching the MB to the base socket.
2) Loosen the two screws (M3 × 16) attaching the Trans-
ducer body to its base socket to separate them.
3) Mount the base socket onto the MB with the two screws
(M4 × 20) provided with the Transducer. Be sure to in-
sert the gasket between them.
4) Install the MB-base socket assembly to a panel surface
with the attached 2 pan-head screws (M4 × 60).
5) Attach the pressure supply pipe referring to ‘Piping.’
6) Plug the Transducer body into its base socket and fasten
the M3 screws which had been loosened in the above pro-
cedure (2).
■
MB-P1
1) Remove the closing panel. Be sure to keep the gasket at-
tached to the closing panel so that it will be reused when
attaching the MB-P1 to the base socket.
2) Install the MB onto a panel surface with the attached 2
pan-head screws (M4 × 40).
3) Loosen the two screws (M3 × 16) attaching the Trans-
ducer body to its base socket to separate them.
4) Mount the base socket onto the MB with the two screws
(M4 × 20) provided with the Transducer. Be sure to in-
sert the gasket between them.
5) Attach the pressure supply pipe referring to ‘Piping.’
6) Plug the Transducer body into its base socket and fasten
the M3 screws which had been loosened in the above pro-
cedure (3).
Note: Put the closing panel back and the gasket onto the MB if
the base socket is not attached immediately.
MB
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-3430 Rev.2 P. 3 / 5