        Screw attaching 

        the base to the MB

(included in the transducer)

Screw attaching the body 

to the base

(included in the transducer)

Screw attaching the body 

to the base

(included in the transducer)

Closing Panel

Base socket

(included in the transducer)

■ 

MB-08 or MB-16

Base socket

(included in the transducer)

        Screw attaching 

        the base to the MB

(included in the transducer)

Gasket

I/P Transducer Body
(P-UNIT)

I/P Transducer Body
(H-UNIT)

Specifications

Mounting Screw

Mounting Block

INSTALLATION

Secure an appropriate environment before installing the 
Mounting Block and I/P Transducer.  Refer to ‘Component 
Identification’ and ‘Mounting Requirement.’
The Mounting Block, except for the model MB-P1, can be 
mounted on the Standard Rack Mounting Frame model BX-
16H which fits into 19-inch rack.

 

MB-01

The MB-01 is designed to be fixed together with the base 
socket of the transducer by the same screws.  Get the H-
UNIT Series I/P Transducer ready at hand when installing 
the MB-01.

1) Remove the closing panel.  Be sure to keep the gasket at-

tached to the closing panel so that it will be reused when 

attaching the MB to the base socket.

2) Loosen the two screws (M3 × 16) attaching the Trans-

ducer body to its base socket to separate them.

3) Mount the base socket onto the MB with the two screws 

(M4 × 20) provided with the Transducer.  Be sure to in-

sert the gasket between them.

4) Install the MB-base socket assembly to a panel surface 

with the attached 2 pan-head screws (M4 × 60).

5) Attach the pressure supply pipe referring to ‘Piping.’
6) Plug the Transducer body into its base socket and fasten 

the M3 screws which had been loosened in the above pro-

cedure (2).

 

MB-P1

1) Remove the closing panel.  Be sure to keep the gasket at-

tached to the closing panel so that it will be reused when 

attaching the MB-P1 to the base socket.

2) Install the MB onto a panel surface with the attached 2 

pan-head screws (M4 × 40).

3) Loosen the two screws (M3 × 16) attaching the Trans-

ducer body to its base socket to separate them.

4) Mount the base socket onto the MB with the two screws 

(M4 × 20) provided with the Transducer.  Be sure to in-

sert the gasket between them.

5) Attach the pressure supply pipe referring to ‘Piping.’
6) Plug the Transducer body into its base socket and fasten 

the M3 screws which had been loosened in the above pro-

cedure (3).

Note:  Put the closing panel back and the gasket onto the MB if 

the base socket is not attached immediately.

MB