![background image](http://html1.mh-extra.com/html/m-system/m3lt/m3lt_instruction-manual_3220352007.webp)
M3LT
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: [email protected]
EM-2661-A P. 7 / 7
■
OUTPUT TYPE & RANGE
TABLE 9
OUTPUT TYPE
MINIMUM SPAN
MAXIMUM RANGE
CONFORMANCE RANGE
DC Current
DC Voltage, Narrow Spans
DC Voltage, Wide Spans
1mA
250mV
1V
0 to 20mA
-2.5 to +2.5V
-10 to +10V
0 to 24mA
-3 to +3V
-11.5 to +11.5V
■
INPUT
OUTPUT
I/O Range Label (included in the product package)
I/O RANGE LABEL
Blank I/O range labels are included in the product package.
Write in the configured ranges and put the label on the side as
shown below.
STATUS INDICATOR LED
Combinations of the three front LEDs (LD1, LD2, LD3) in-
dicate the transmitter’s operating status by different blink-
ing patterns.
Examples are shown below.
LD1
LD2
LD3
A
A
A
LD1
LD2
LD3
G
LD1
LD2
LD3
G
LD1
LD2
LD3
LD1
LD2
LD3
A
LD1
LD2
LD3
A
G
G
LD1
LD2
LD3
A
G
LD1
LD2
LD3
A
A
A
R
R
R
G
NORMAL OPERATION (RUN) MODE
ERROR MODE
System Error
Indicates the CPU’s communication error.
DIP SW Error
DIP SW configuration is inappropriate.
Check the DIP SW setting referring to Tables 2 – 7.
Burnout in PC Configuration Mode (Option A)
Burnout in DIP SW Configuration Mode
PC Configuration RUN Mode (Option A)
The transmitter is configured via PC and
is in normal operating conditions.
DIP SW Configuration RUN Mode
The transmitter is configured via DIP SW and
is in normal operating conditions.
Output Saturated in PC Configuration Mode
(Option A)
The output is below -15% or above +115%.
Output Saturated in DIP SW Configuration Mode
The output is below -15% or above +115%.
Amber LED
Green LED
Red LED
OFF
ON
Blink
A
G
R