TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
+
–
+
–
CONFIGURATOR
JACK
7
8
11
12
OUTPUT
POWER
4
+
–
T / C
ext. leadwire
+
*The CJC Sensor is secured to the terminal 6.
Loosen only the terminal 4 – 5 and connect the T/C extension wires.
–
CJC
SENSOR
*
5
6
■
CJC SENSOR TERMINAL BLOCK
CJC Sensor Terminal Block
White Dot
Serial No.
Be careful not to separate the Sensor from the
terminal block. If you did, connect the CJC leg
marked with a white dot to the terminal 6 and
the other leg to the terminal 5.
The CJC Sensor is calibrated to a particular
unit and not interchangeable with another.
Match the Serial No. of the unit and the sensor.
■
WIRING INSTRUCTIONS
• Applicable wire size
Solid:
0.2 to 2.5 mm
2
(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm
2
Tinning wire ends may cause contact failure
and therefore is not recommended.
Ferruled: 0.2 to 1.5 mm
2
(0.55 to 1.35 dia.)
The following Phoenix Contact terminals are
recommended:
AI 0,25-8YE
0,2 to 0.25 mm
2
AI 0,34-8TQ
0,25 to 0.34 mm
2
AI 0,5-8WH
0,34 to 0.5 mm
2
AI 0,75-8GY
0,5 to 0.75 mm
2
AI 1,0-8RD
0,75 to 1.0 mm
2
AI 1,5-8BK
1,0 to 1.5 mm
2
• Expose wire conductors by 8 mm (0.31”).
8 mm
8 mm
4 mm dia.
max.
4 mm dia.
max.
Wire exposure
Recommended
ferruled wire
EXTERNAL DIMENSIONS
mm (inch)
10 11 12
7
8
9
4
5
6
106 (4.17)
18 (.71)
7
(.28)
110.5 (4.35)
62 (2.44)
[5 (.20)]
• When mounting, no extra space is needed between units.
DIN RAIL
35mm wide
CJC SENSOR
(model: CJM)