background image

M2XRP2

P. 5 / 5

EM-5059 Rev.5

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such 
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive 
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this 
warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original 
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED 
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR 
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

STATUS INDICATOR LED

The M2XRP2 is provided with a status indicator LED which 
lashes in different patterns indicating various status of its 
CPU.
When it is functioning within normal parameters, the LED 
lashes in a regular pattern of ON and OFF.  The high levels 
mean that the light is ON, while the low levels means OFF 
for as shown in the igure below.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 20 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the  “ADJUST-
MENT PROCEDURE” explained earlier.

CHANGING I/O TYPE & RANGE

Input  type  and  range,  and  output  type  and  range  can  be 
programmed  on  the  Coniguration  Software.   Additionally, 
when changing the input type, hardware settings are need-
ed as explained below.

■฀

■฀

LEFT SIDE VIEW (with cover removed)

1

4
3
2
1

2

3

4

ON

ON

OFF

OFF ON OFF

ON OFF

SW3

SW1

SW2

SW4

Input Selector SW

Output Selector SW

1
2

1
2

• Output Type

OUTPUT TYPE 

SW4-4  SW4-3  SW4-2  SW4-1

0 – 20mA DC (*) 

OFF 

ON 

OFF 

OFF

-2.5 – 2.5V DC 

ON 

OFF 

OFF 

ON

-10 – +10V DC 

ON 

OFF 

ON 

OFF

 DIP SWITCH SETTINGS

 (*) Factory setting

Pulse  sensing  and  noise  ilter  settings  are  invalid  for  RS-
422 line driver input.

• Input Type

INPUT TYPE 

SW1-2  SW1-1  SW2-2  SW2-1

Open collector (*) 

OFF 

OFF 

OFF 

OFF

Voltage pulse 

OFF 

OFF 

OFF 

OFF

RS-422 line driver 

ON 

ON 

ON 

ON

 Pulse Sensing

PULSE SENSING 

SW3-4 

SW3-2

Capacitor coupled *

2

 

OFF 

OFF

DC coupled (*) 

ON 

ON 

*2. Frequency range must be 0 – 100 Hz or higher.  0 – 1 
kHz or higher for sinusoidal waveform input.  Frequencies 
lower than ±10 Hz may be out of accuracy conformance.

• Noise Filter

NOISE FILTER 

SW3-3 

SW3-1

With 

ON 

ON

W/O (*) 

OFF 

OFF

Be sure to apply the noise ilter appropriate for the selected 
frequency range as shown in the table below.  The accuracy 
may not be assured if no ilter is applied.

 

FREQUENCY RANGE 

NOISE FILTER TYPE

 

0 –   10 mHz 

With 

 

 

0 – 100 mHz 

With

 

0 –     1 Hz 

With 

 

 

0 –   10 Hz 

W/O 

 

 

0 – 100 Hz 

W/O

 

0 –     1 kHz 

W/O 

 

 

0 –   10 kHz 

W/O 

 

 

0 – 100 kHz 

W/O

Normal operation

Operating Mode

LED Flashing Pattern

Zero adjustment

Span adjustment

Programming

Abnormal operation

80 msec.