M2XRP2

P. 3 / 5

EM-5059 Rev.5

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Check DIP switch setting.
3)  Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

4)  Input:  Check that the input voltage is within 0 – 100% of 

full-scale.

5)  Output:    Check  that  the  load  resistance  meets  the  de-

scribed speciications.

6)  Status indicator LED:  Check that it lashes in the nor-

mal patterns.

ZERO/SPAN ADJUSTMENTS

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
speciications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, ine zero and span adjustments can 
be  done  to  ±5%  by  pressing  UP/DOWN  switches  enabled 
with  the  zero/span  selector  switch.    Calibrated  values  are 
stored  in  the  non-volatile  memory,  which  will  not  be  lost 
even when you turn off power supply to the unit.
Zero and span are respectively set to 0% and 100% at the 
factory.

 FRONT VIEW (with cover open)

Zero/Span Selector
  ZERO

:  

UP/DOWN switches usable for zero adjust-
ment.

  OFF

:  

UP/DOWN switches unavailable.

  SPAN

:  

UP/DOWN switches usable for span adjust-
ment.

UP/DOWN Switches
  UP

:  

Pressing UP increases adjusted values.

  DOWN

:  

Pressing DOWN decreases adjusted values.

 HOW TO CALIBRATE THE ZERO

Slide  the  Zero/Span  Selector  to  the  bottom  position  and 
press  UP  or  DOWN  switch.    Incrementing  speed  will  be 
doubled when you keep pressing a switch.

 HOW TO CALIBRATE THE SPAN

Slide  the  Zero/Span  Selector  to  the  top  position  and  press 
UP or DOWN switch.  Incrementing speed will be doubled 
when you keep pressing a switch.

 HOW TO RESET

After  you  calibrated  manually  with  these  switches,  you 
can reset them to its ex-factory state by pressing both UP/
DOWN switches at once.

 ADJUSTMENT PROCEDURE

Use a signal source and measuring instruments of suficient 
accuracy level.  Turn the power supply on and warm up for 
more than 20 minutes.
1)  ZERO:    Apply  0%  input.    Slide  the  Zero/Span  Selector 

to the bottom position.  Press UP or DOWN switch and 
adjust output to 0%.

2)  SPAN:  Apply 100% input  Slide the Zero/Span Selector 

to the top position.  Press UP or DOWN switch and ad-
just output to 100%.

3)  Check ZERO adjustment again with 0% input.
4)  The  ZERO  and  SPAN  adjustments  are  processed  in 

a  digital  processor,  and  therefore  they  do  not  interact.  
However,  if  ZERO  value  is  changed,  repeat  the  above 
procedure 1) – 3).

UP/DOWN Switches

The front cover cannot be opened to 180 deg. 
when flush with neighboring units.

Configurator Jack

■฀

■฀

Input Monitor LED, PL1

Input Monitor LED, PL2

Status Indicator LED

Zero/Span Selector

Top: SPAN
Middle: OFF
Bottom: ZERO

CONFIGURATOR

JACK

+

OUTPUT

7

8

U(+)

V(–)

POWER

10

11

+

OUTPUT

7

8

U(+)

V(–)

POWER

10

11

CONFIGURATOR

JACK

ROTARY
ENCODER

ROTARY
ENCODER

■฀

RS-422 LINE DRIVER INPUT

■฀

OPEN COLLECTOR, VOLTAGE INPUT

4

+ 1

5

2

+

+

A

φ

B

COM

φ

PWR

+

1

2

+

3

6

A

φ

PWR

A

φ

COM

+

4

5

B

φ

B

φ

Reviews: