SELF-SYNCH TRANSMITTER

(PC programmable)

MODEL

M2EXS

OPERATING MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner (body + base socket) .............................(1)

 

MODEL NO.

Confirm Model No. marking on the side of the product to be 
exactly what you ordered.

 

OPERATING MANUAL

This manual describes detailed operation regarding settings.
The M2EXS is programmable using a PC.  For detailed in-
formation on the PC configuration, refer to the M2ECFG 
users manual (EM-5147).
The M2ECFG Configurator Software is downloadable at 
M-System’s web site: http://www.m-system.co.jp

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2 and  In-

stallation Category II.  Reinforced insulation (signal in-
put or output to power input: 300V) and basic insulation 
(signal input to output: 300V) are maintained.  Prior to 
installation, check that the insulation class of this unit 
satisfies the system requirements.

• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:
  100 – 120V AC rating: 85 – 132V, 47-66 Hz, ≤ 5VA
  200 – 240V AC rating: 170 – 264V, 47-66 Hz, ≤ 7VA

 

GENERAL PRECAUTIONS

Before you remove the unit from the socket or mount it, 
turn off the power supply and input signal for safety.

 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 10 to 85% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

• With voltage output, do not leave the output terminals 

shortcircuited for a long time. The unit is designed to en-
dure it without breakdown, however, it may shorten ap-
propriate life duration.

• The edge of the display may be hidden by the frame and 

invisible depending on the view angle.

COMPONENT IDENTIFICATION

Connection Diagram

(Side)

Body

Base Socket

Display

Fixing Screw

(screw for attaching 
the body to the socket)

Mode

Set

Up

Down

Specification

Summary of Contents for M2EXS

Page 1: ...f this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity...

Page 2: ...ving the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to the drawings in the shown below TERMINAL CONNECTIONS Connect the unit as in the diagram bel...

Page 3: ...ing changeable state used to enter save the setting value Used to move on through digits of setting value for input output scaling at setting changeable state Up Button Used to shift through setting p...

Page 4: ...tting of the Advanced mode for settings DISPLAY IN EACH SETTING MODE For each setting current values of setting parameter ITEM number and setting value are indicated During setting Setting is indicate...

Page 5: ...RT POWER ON Measuring Mode Hold down Mode Button for 2 seconds Hold down Mode Button for 2 seconds Basic Setting Mode Option Mode Advanced Mode Hold down Mode Button for 2 seconds Hold down Mode Butto...

Page 6: ...ing value to set value Keeping pressing Down button enables to decrease the value continuously Operation of input setting parameter 06 Angle offset is set by teach The present input value is displayed...

Page 7: ...ds Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Do...

Page 8: ...input scaling 99999 999999 100 00 16 Input decimal point No decimal point The number of decimal places 1 5 2 places of decimals 17 Output range 0 20mA 5 5V 10 10V 0 20mA 18 0 output setting 0 000 19 0...

Page 9: ...the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output 0 20 mA DC 0 20 mA 5 5 V Output 5 5 V DC 10 10 V Output 10 10 V DC When output range is changed turn the power off and then set the outp...

Page 10: ...ase it by pressing Up and Down button Press and hold them enables to change value continuously 1 Pressing and holding Mode button more than 2 seconds or turning off the power enable to exit loop test...

Page 11: ...ble unit Set Set Hold down Mode button for 4 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 0 30 5 000 5 00...

Page 12: ...to user s unit setting display A unit can be created by using any characters Up to 13 characters available 1 Up and Down button enables to move on selected characters Set button enables to select a ch...

Page 13: ...wn Mode button for 6 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 4 0 1 60 OFF RESET Lock Unlock Advanced Mode Parame...

Page 14: ...Adjust brightness of display It is available to set the range between 1 darkest 4 brightest Initial value 4 92 Display timeout Set the time to off the display when there is no operation within a certa...

Page 15: ...de button for 8 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 32 5 00...

Page 16: ...een 5 to 105 for both X and Y For X it is required to set in ascending order from X001 Be sure that if it is set with other than ascending order cor rect conversion is not carried out Initial value X0...

Page 17: ...rror occurs only high priority error is displayed Order of priority is EEPROM ERROR OVER RANGE SCALING ERROR in descending order ERROR MESSAGES DISPLAY SETTING INPUT ENGINEERING UNIT VALUE INPUT SCALI...

Page 18: ...ed in the users manual of the M2ECFG configurator software Or follow the procedure shown below INPUT FINE ADJUSTMENT Set the input signal to 0 and adjust the input to 0 by 06 Angle offset OUTPUT FINE...