M1EXV-4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6040-B Rev.2 P. 14 / 37
• Parameters
MODE
ITEM
SETTING PARAMETER
RANGE
UNIT
INITIAL VALUE
Ch2 Setting
01
Lockout setting
Lock / Unlock
–
Lock
102
Ch2 Enable
Disable / Enable
–
Enable
111
Ch2 Input range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
-5 – +5 V
112
Ch2 0% Input setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
1.000
113
Ch2 100 % Input setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
5.000
114
Ch2 0 % Input scaling
-99999 – 999999
–
0.00
115
Ch2 100 % Input scaling
-99999 – 999999
–
100.00
116
Ch2 Input decimal point
No decimal point
The number of decimal places: 1 – 5
–
2 places of decimals
117
Ch2 Unit (INP Scaling)
Choose from 68 types
–
%
161
Ch2 Output range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
0 – 20 mA
162
Ch2 0 % Output setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
4.000
163
Ch2 100 % Output setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
20.000
171
Ch2 Filter time constant
0 – 30
sec.
0
181
Ch2 Input zero fine adjust
-5.000 – 5.000
%
0.000
182
Ch2 Input span fine adjust
95.000 – 105.000
%
100.000
191
Ch2 Output zero fine adjust
-5.000 – 5.000
%
0.000
192
Ch2 Output span fine adjust
95.000 – 105.000
%
100.000
195
Ch2 User’s table linearization Cancel / Set
–
Cancel
198
Ch2 Loop test
-5.00 – 105.00
%
Cancel
[01] Lockout setting
Enable / disable Lockout setting.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Lock
Enable Lockout setting
Lock
Unlock
Disable Lockout setting
When Lockout setting is enabled, it is possible to shift to
each setting mode and confirm the setting value of each
setting parameter item. Each parameter item display in-
dicates ‘DATA (Locked)’ when set to ‘Lock’, and indicates
‘DATA’ when set to ‘Unlock’.
[102] Ch2 Enable
Enable / disable Ch2.
No output signal or present value is displayed for the disa-
bled channel in Measuring Mode.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Disable
Disable Ch2
Enable
Enable
Enable Ch2
Even when Ch2 is disabled, parameter settings for Ch2 can
be performed.
[111] Ch2 Input range
Set the input range.
SETTING VALUE DESCRIPTION
INITIAL VALUE
0 – 20 mA
Input: 0 – 20 mA DC
-5 – +5 V
-5 – +5 V
Input: -5 – +5 V DC
-10 – +10 V
Input: -10 – +10 V DC
When the input range is changed, turn the power off, and
change the connection to the input terminal of the unit ac-
cordingly. Note that input setting values are changed to the
initial values.
[112] Ch2 0 % Input setting
Set the 0 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
0.00 – 19.00
1.00
4.00
-5 – +5 V
-5.000 – 4.750
0.250
1.000
-10 – +10 V
-10.000 – 9.000
1.000
-10.000
Set as follows.
[112] 0 % input setting < [113] 100 % input setting
[113] Ch2 100 % Input setting
Set the 100 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
1.00 – 20.00
1.00
20.00
-5 – +5 V
-4.750 – 5.000
0.250
5.000
-10 – +10 V
-9.000 – 10.000
1.000
10.000
Set as follows.
[112] 0 % input setting < [113] 100 % input setting
[114] Ch2 0 % Input scaling
Set the display value of 0 % input setting.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
0.00
[115] Ch2 100 % Input scaling
Set the display value of 100 % input setting.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
100.00