M1EXV-4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6040-B Rev.2 P. 12 / 37
[95] Ch1 User’s table linearization
Enable / Disable Linearization function using a user specified table.
Press Set button and confirm that ‘Cancel” is displayed with blinking.
Press Up or Down button to change to ‘Set’, and press Set button to shift to Ch1 Linearization mode.
Note: Be sure to set the Lockout setting to ‘Unlock’ before shifting to Ch1 Linearization mode.
ITEM
95
ITEM
95
DATA (Setting)
DATA (Setting)
ITEM
95 - 001
Up/Down
button
Set button
Set
Disable
Cancel
Ch1 User‘s table linearization
Ch1 User‘s table linearization
Ch1 Linearization enable
[98] Ch1 Loop test
Output signal can be simulated for performing loop test.
Press Set button and confirm that ‘Cancel’ is displayed with blinking.
Press Up or Down button to change to ‘Set’, and press Set button to shift to Loop test display.
The present value is indicated. Increase or decrease it by pressing Up or Down button.
Holding down each button changes the value continuously.
Hold down Mode button for ≥ 2 seconds or turn off the power to exit loop test.
ITEM
98
Ch1 Loop test
ITEM
98
DATA (Setting)
DATA (Setting)
Ch1 Loop test
Ch1 Loop test
Up/Down
button
Set button
Set
mA
4.000
0.00
%
Cancel
OUtput engineering value
Output % value
Note: While the loop test is performed, all input signals are disregarded.
When ‘Display timeout’ is activated and the display has been cleared (display off) during loop test, press any front button to