![M-system M1EXV-4 Operating Manual Download Page 8](http://html1.mh-extra.com/html/m-system/m1exv-4/m1exv-4_operating-manual_3197458008.webp)
M1EXV-4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6040-B Rev.2 P. 8 / 37
■
OPERATION IN EACH SETTING MODE
• Basic operation
Mode button:
In Measuring mode, hold down Mode button for ≥ 1.5 seconds, ≥ 3 seconds, ≥ 4.5 seconds, ≥ 6 seconds, or
≥ 7.5 seconds to shift to the respective setting modes.
In each setting mode, hold down Mode button for ≥ 2 seconds to return to Measuring mode.
While in each setting mode, press Mode button to shift to the setting mode for the next channel.
Hold down Mode button for ≥ 2 seconds during setting ( ‘(Setting)’ is displayed next to ‘DATA’) to discard
the set value and to return the value to the value before setting change (‘(Setting)’ next to ‘DATA’ is
cleared).
Set button:
By pressing Set button at each setting parameter item, the setting value starts blinking and becomes
changeable (‘(Setting)’ is indicated next to ‘DATA’.).
During setting change, press Set button to save (enter) the setting value. and confirm that the value that
was blinking turns ON.
Up button:
Press Up button to shift through setting parameter items.
During setting change, press Up button to select the setting value or increase the numerical value.
Keeping pressing Up button increases the value continuously.
Down button:
Press Down button to shift through setting parameter items.
During setting change, press Down button to select the setting value or decrease the numerical value.
Keeping pressing Down button decreases the value continuously.
Note: DO NOT press 2 or more buttons simultaneously.
• Setting numerical parameter
When setting a numerical parameter, the value need to be set digit by digit.
Each time Set button is pressed, the next digit starts blinking.
At the blinking digit, change the numerical value with Up and Down buttons.
By keeping pressing Up or Down button while the digit is blinking, the value of the digit continuously increases or decreases
to the maximum or minimum.
Each time Set button is pressed, the blinking digit moves from the least significant to the most significant in order.
When Set button is pressed at the most significant digit, the digit that was blinking turns ON, and the setting value is saved.
During setting, to discard the setting value change, hold down Mode button for ≥ 2 seconds.
ITEM
14
DATA
0
Ch1 0% input
ITEM
14
DATA (Setting)
DATA (Setting)
DATA (Setting)
Ch1 0% input
ITEM
14
Ch1 0% input
ITEM
14
Ch1 0% input
Set button
Setting first digit
Setting fifth digit
Setting sixth digit
Set button (save)
Set button
Set button
000000
000000
000000
• Lockout setting
‘The unit has ‘Lockout setting’ function.
To disable the lockout setting, shift to the setting parameter ITEM 01 ‘Lockout Setting’ in each setting mode and set to ‘Un-
lock’.
To enable ‘Lockout Setting’ again, set to ‘Lock’.
Even when ‘Lockout Setting’ is enabled, each setting value can be confirmed.
Confirm that ‘DATA (Locked)’ is indicated in such a time.