![background image](http://html1.mh-extra.com/html/m-system/ethercat-r7i4dect-1-yvf4/ethercat-r7i4dect-1-yvf4_instruction-manual_3116652002.webp)
R7I4DECT-1-YVF4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7779-K P. 2 / 10
COMPONENT IDENTIFICATION
■
FRONT VIEW
Fixed Address Setting Rotary SW
Status Indicator LED
RJ-45 Modular jack for
EtherCAT communication
PC Configurator Jack
ECT OU
T
ECT IN
CNFG.
X16
Dev. ID
PWR
RUN
ERR
L/A IN
L/A OUT
Y0
Y1
Y2
Y3
X1
0 1 2
3
4
56
78
9A
B
C
D
EF
0 1 2
3
4
56
78
9A
B
C
D
EF
Power Supply
Terminals
Output Terminals
1
4
OUTPU
T
■
STATUS INDICATOR LED
ID
FUNCTION
COLOR STATUS
Power
Internal power
Green
Off
Error
On
Normal
RUN
Device state
Green
Off
INIT
Blinking
PRE-OPERATIONAL
Single Flash
SAFE-OPERATIONAL
On
OPERATIONAL
ERR
Error
Red
Off
No error
Blinking
Invalid Configuration
Single Flash
Local error
Double Flash
Process data watchdog timeout/
EtherCAT watchdog timeout*
1
On
Application controller failure
L/A IN
IN port status
Green
Off
No Link
Flickering
Link and activity
On
Link without activity
L/A OUT
OUT port status
Green
Off
No Link
Flickering
Link and activity
On
Link without activity
*1. Watchdog timeout is disabled for input-only slaves like R7I4DECT-1-SVF8N according to the EtherCAT specification.
Blinking
200ms-On, 200ms-Off
Single flash
200ms-On, 1000ms-Off
Double flash
200ms-On, 200ms-Off, 200ms-On, 1000ms-Off
Flickering
50ms-On, 50ms-Off
■
FIXED ADDRESS SETTING ROTARY SW (ID selector)
Fixed address 1 to 255 can be set using the two rotary
switches each marked 0 to F in combination.
When fixed address is not used, set the switches to 0.
Settable range: 0 to 255
Factory default: 0
Fixed Address Setting (x1)
Fixed Address Setting (x16)
0123
45
678
9AB
C
D
EF
0123
45
678
9AB
C
D
EF