EM-8274 P. 13 / 18
■
PDO Assign Objects ( (Data Transmission Order, Output: 0x1C12, Input: 0x1C13)
An allocation list for RxPDO and an allocation list for TxPDO are created in 0x1C12 and 0x1C13, respectively.
The indexes stored in 0x1C12 and 0x1C13 are placed in the order they are actually transmitted via PDO.
• PDO group
Assignment of the PDO groups is based on the I/O card types as defined by Information Data Objects.
•PDO group 0: Status
•PDO group 1: Analog I/O card
•PDO group 2: Discrete I/O card
The PDO group data is transmitted in the following order of priority: Group 0 > Group 1 > Group 2.
Table 10 shows the PDO list for the card configuration example of Table 5
Table 10: PDO List for the Configuration Example of Table 5
INDEX
SUB-INDEX
DATA TYPE
BIT
ACCESS
PDO GROUP
VALUE
CONTENT
0x1C12
0
UINT8
8
RO
–
5
Number of items
1
UINT16
16
RO
1
0x1603
Analog output data
2
UINT16
16
RO
1
0x1605
Analog output data
3
UINT16
16
RO
1
0x1607
Analog output data
4
UINT16
16
RO
1
0x1608
Analog output data
5
UINT16
16
RO
2
0x1601
Discrete output data
0x1C13
0
UINT8
8
RO
–
6
Number of items
1
UINT16
16
RO
0
0x1AFF
Status data
2
UINT16
16
RO
1
0x1A02
Analog input data
3
UINT16
16
RO
1
0x1A04
Analog input data
4
UINT16
16
RO
1
0x1A06
Analog input data
5
UINT16
16
RO
1
0x1A08
Analog input data
6
UINT16
16
RO
2
0x1A00
Discrete input data
■
Sync Manager Type (0x1C00)
Sync Manager Type is allocated to object 0x1C00 based on the EtherCAT specification. (Refer to Table 11.)
Table 11: Object configuration for 0x1C00
INDEX
SUB-INDEX
DATA TYPE
BIT
ACCESS
VALUE
CONTENT
0x1C00
0
UINT8
8
RO
4
Number of items
1
UINT8
8
RO
1
Mailbox Write
2
UINT8
8
RO
2
Mailbox Read
3
UINT8
8
RO
3
Process Output Data
4
UINT8
8
RO
4
Process Input Data
■
Sync Manager Parameter Objects (0x1C32, 0x1C33)
Setting object for Sync Mode.
Objects 0x1C32 and 0x1C33 are fixed as R3-NECT1 only supports the Free Run mode.
Distributed Clock (DC) mode is not supported.