CHECKING

  1 ) Terminal wiring:  Check that all cables are correctly 

connected according to the connection diagram.

  2 ) Power input voltage:  Check voltage across the termi-

nal 7 – 8 with a multimeter.

  3 ) Input:  Check that the input signal is within 0 – 100% 

of the full-scale.

  4 ) Alarm operations:  Check the alarm operations refer-

ring to the figure below.

  5 ) Output load:  Check that the output rating road is: 

Output code 2 and 3: 240 V AC / 120 VA or 30 V DC / 

30 W  

Output code 5: 240 V AC / 600 VA or 30 V DC / 150 W 

Output code 2A, 3A and 5A: 220 V DC / 30 W 

For maximum relay life with inductive load, external 

protection is recommended.

0

50

100

Input
(%)

LL

L

HH

H

L2 (1–2)

ON

L3 (1–3)

ON

L4 (9–11)

ON

OFF

OFF

L1 (9–10)

ON

OFF

OFF

Alarm Trip Operation

                   

Terminal No. in parentheses

Example with quad N.O. contacts (LL, L, H, HH)

Trip Operation in Power Failure

• Output code 2, 2A: All relays turn off.
• Output code 3, 3A: All relays turn on.
• Output code 5, 5A: Terminals 1 – 3, 9 – 11 turn on.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• 

H (HH) Setpoint

Increase the input signal from a value lower than the set-
point and check that the relay trips at the H (or HH) set-
point within the setpoint accuracy described in the data 
sheet.

• 

L (LL) Setpoint

Decrease the input signal from a value higher than the set-
point and check that the relay trips at the L (or LL) setpoint 
within the setpoint accuracy described in the data sheet.
When the setpoints are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

In order to protect the unit from lightning surges entering 
through power supply cables, use of appropriate lightning 
surge protectors are recommended.  Please contact M-Sys-
tem.