AS4V
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: [email protected]
EM-1609 Rev.15 P. 3 / 5
FRONT VIEW & PROGRAMMING
■
L1
L2
L3
L4
ALARM
DATA
ITEM
DATA
ITEM
ITEM No. Display
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
*
Monitor LEDs
DATA Display
*
L3 or L4 does not turn on for dual output type.
PROGRAMMING PROCEDURE
1 ) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2 ) Press DATA UP or DOWN key and choose “1” or “2” on DATA
display.
1 : Only alarm setpoints are modifiable.
2 : All parameters are modifiable.
3 ) Press ITEM UP or DOWN key until ITEM display shows the
ITEM No. you need to change.
4 ) Press DATA UP or DOWN key and choose a DATA No. or value
you need on DATA display.
5 ) Repeat above 3 and 4. (Entered data is stored when you move to
a new ITEM.)
6 ) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7 ) Press DATA UP or DOWN key and choose “0” on the display.
8 ) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input.
(You can now check data setting by choosing ITEM No.)
Note: DO NOT press UP and DOWN keys simultaneously.
ITEM
MDF.
CODE
DATA
CONTENTS
DEFAULT SETTING
P
N/A
-1999 – 9999
Process input display in engineering unit (as set in ITEM 07, 08)
----
L1
L2
L3
L4
1, 2
1, 2
1, 2
1, 2
-1999 – 9999*
1
-1999 – 9999*
1
-1999 – 9999*
1
-1999 – 9999*
1
L1 alarm setpoint in engineering unit
L2 alarm setpoint in engineering unit
L3 alarm setpoint in engineering unit *
2
L4 alarm setpoint in engineering unit *
2
Quad: 20.0
Quad: 30.0
Quad: 70.0
Quad: 80.0
Dual: 20.0
Dual: 80.0
01
0, 1, 2
Modification code
0 : Data indication only.
1 : Only ITEM L1 – L4 are modifiable.
2 : All parameters are modifiable.
1
02
N/A
0 – 99
Status indication (“0” is normally indicated.)
0: Normal 1: Memory error 10: Out of input range -15 – +115%
03
N/A
0, 1, 4
Input range
0: S1, 1: S2, 4: Z1
Specified when ordering
04
N/A
-15.0 – 115.0
Input indicated in % (as set in ITEM27, 28)
----
05
06
2
2
-19.99 – 99.99
0.000 – 9.999
Zero adjustment (%) (fine adj. of the value set in ITEM 27)
0.00
Gain adjustment (fine adj. of the value set in ITEM 28)
1.000
07
08
2
2
-1999 – 9999
-1999 – 9999
Display range scaling 0% *
3
Display range scaling 100% *
3
0.0
100.0
09
2
0, 1, 2, 3
Decimal point position
(Specify the number of digits)
0 : _ _ _ _
1 : _ _ _ . _
2 : _ _ . _ _
3 : _ . _ _ _
1
10
2
0 – 99
Power ON-delay time (seconds)
5
11
2
0 – 999
Alarm ON-delay time (seconds)
0
12
2
0, 1, 2, 3, 4
Moving average (sampling cycle: 100 msec.)
0: No, 1: 4 samples, 2: 8 samples, 3: 16 samples, 4: 32 samples
0
13
14
15
16
2
2
2
2
0, 1
0, 1
0, 1
0, 1
L1 trip operation
L2 trip operation
L3 trip operation
L4 trip operation
(0: Lo, 1: Hi)
(0: Lo, 1: Hi)
(0: Lo, 1: Hi) *
2
(0: Lo, 1: Hi) *
2
Quad: 0
Quad: 0
Quad: 1
Quad: 1
Dual: 0
Dual: 1
17
2
0, 1 – 60
Power-saving mode 0: Continuous display*
4
1 – 60: Time before display turned off (minutes)
10
18
19
20
21
2
2
2
2
0, 1
0, 1
0, 1
0, 1
L1 coil at alarm (0: Energized, 1: De-energized)
L2 coil at alarm (0: Energized, 1: De-energized)
L3 coil at alarm (0: Energized, 1: De-energized)*
2
L4 coil at alarm (0: Energized, 1: De-energized)*
2
0
0
0
0
22
N/A
----
Version No. indication
----