12
Usvk13
reduction 200/130 to 150/100
Instructions for installation and use DIAMOND Gas 550V-DV-850V-DV-1150V
Picture 3: WALL EXIT (C11)
IMPORTANT
:
Be carefull every horizontal part does not have a negative in
clination in direction of the outlet. It is even better, when possible to
have a little inclination of 2 or 3 degrees ascending to avoid rain and
condenstation in the tube. Install wall outlet like fig 1
Picture 3
Picture 4
Picture 5
Ø 150/100
With reduction usvk13 on appliance (Pic 3 )
Appliance
A (min)
B (min)
B (max)
Position air inlet
850V
550V
1,25m
0,75m
Wall Exit
A+0,5m
4
850DV
550DV
1,25m
0,75m
Wall Exit
A
4
1150V
1,25m
Wall Exit
A
4
(A) ø 200/130 in combinatie met / combiné
avec (b) ø 150/100
With reduction usvk13 placed horizontaly after curve 90° ( Pic. 4 )
Appliance
A (min)
Ø 200/130
B (min)
Ø 150/100
B (max)
Ø 150/100
Position air inlet
850V
550V
1m
0,75m
Wall Exit
A+ ”USVK13” +4m
4
850DV
550DV
1m
0,75m
Wall Exit
A+ ”USVK13” +3m
4
1150V
1m
Wall Exit
A+ ”USVK13” +3m
4
ø 200/130 (
pic.5
)
Appliance
A (min)
B (min)
B (max)
Position air inlet
850V
550V
1m
0,75m
Wall Exit
A+8m
3
850DV
550DV
1m
0,75m
Wall Exit
A+7m
3
1150V
1m
Wall Exit
A+7m
3
Summary of Contents for DIAMOND Gas 550V
Page 22: ...LUNA 850 DV GAS Instructions for installation and use DIAMOND Gas 550V DV 850V DV 1150V 22...
Page 40: ...40 Instructions for installation and use DIAMOND Gas 550V DV 850V DV 1150V...
Page 41: ...41 Instructions for installation and use DIAMOND Gas 550V DV 850V DV 1150V 17 CE Certification...
Page 42: ...42 Instructions for installation and use DIAMOND Gas 550V DV 850V DV 1150V...
Page 43: ...43 Instructions for installation and use DIAMOND Gas 550V DV 850V DV 1150V...