139-0647-01.34
Appendix A - Telnet and HTTP Protcols
34
Addresses and status of circuits updated by the command
reply is generated for
Reply to request circuits status command:
Same format as “Request Bus Status”; contains addresses
and status of the circuits speci
fi
ed in the request
command
Reply to request all circuits status command: status of
all circuits
0xB0, 0xB6, byte_1, …, byte_84, 0xF0
byte_i: bits 7-4: status of circuit # 2i, bits 3-0: status of
circuit # 2i-1, i=1-84
Reply to request bus status command: status of all
circuits of the requested bus
0xB0, 0xBE, byte_1, …, byte_11, 0xF0
byte_i format is identical to 3.9, except i=1-11
Circuit status description (4 bits) (3,5 &6 panels only)
Value
1
2
Status
Off
On
Activate zone
0xB0, 0xB7, zone_number_1, …, zone_number_m, 0xF0
zone_number_1, … zone_number_m – numbers of zones to
be activated m<=12
Deactivate zone
0xB0, 0xB8, zone_number_1, …, zone_number_n, 0xF0
zone_number_1, … zone_number_n – numbers of zones to
be deactivated n<=12
Activate/deactivate zone
0xB0, 0xB7, zone_number_1, … zone_number_m, 0xB8,
zone_number_1, …, zone_number_n, 0xF0
zone_number_1, … zone_number_m – numbers of zones
to be activatedzone_number_1, … zone_number_n –
Zone Related Commands