Chapter Five--Control Setup
Individual Momentary Contact ON and
OFF Pushbuttons
Using a standard LynTec SS-2 Switch Set with illuminated
ON switch or two illuminated pushbuttons:
Con
fi
gure the Digital I/O port and link it to a zone as
follows:
1. Follow the previous instructions for naming the contact
closure and setting closure type.
2. Click the M button at the right side of the
fi
rst of the
two ports used. The name box and M button in the
second port should turn gray and the Action selections
should default to Momentary NO. (normally open)
3. Ensure that both of the Action selections for both ports
are set to Momentary NO.
4. Enter a name in the text
fi
eld of the CC used that is
indicative of the zone it will control.
5. Click the “Save Changes” button at the top of the
Onboard I/O box.
6. Follow the previous instructions for assigning a contact
closure to a zone, selecting the merged ports.
7. Click the Save Changes button in the upper left corner
of the Panels page.
Verify proper operation of your Switch Set:
1. Press the ON switch. Circuits in the selected zone
should immediately begin actuating.
2. The ON indicator should
fl
ash steadily until all of the
circuits are in the on state.
3. When the zone has completed, the ON indicator should
remain constantly lit.
4. Press the OFF switch. Circuits in the selected zone
should immediately begin actuating.
5. The ON indicator should
fl
ash steadily until all of the
circuits are in the off state.
6. When the zone has completed, the ON indicator
should remain constantly dark. Note: When using
two illuminate pushbuttons the OFF indicator will
remain constantly lit when the zone has completed.
(OFF indicator will extinguish immediately when ON is
pressed again.)