Control/Monitoring
Emergency Stop
The momentary EMO has two sets of normally closed contacts. Both contacts must be closed
to energize the master control relay coil. Continuity between pins 1 and 2 of the 4 pin Amp
connector external to the unit must also be present. To start the unit, ensure that the EMO is not
depressed, then momentarily press the red POWER ON button located on the control panel
below the EMO. The customer’s EMO, when connected to pins 1 and 2 of the 4 pin Amp
connector, will provide the same functionality. The customer can use pins 3 and 4 of the 4 pin
Amp connector to allow the unit’s EMO to turn off other equipment when properly connected.