Trouble Shooting Guide
Problem
Possible Cause
Possible Remedy
Does not start
Faulty electrical service
Improper voltage and/or phase to
the unit
Transformer breaker is tripped
Circuit breaker in electrical box is
tripped
Main breaker is tripped
Compressor high discharge
pressure shutdown
Compressor motor internal
thermostat tripped
Loss of refrigerant - low suction
pressure shutdown
Check secondary side of 24 volt
transformer. If OK, fault is in control
circuitry. If not OK, fault is in power
supply.
Check Phase Reverse Relay or
Phase Monitor in Electrical box.
Correct phase/voltage as needed.
Reset
Reset
Reset breaker after determining
cause of trip
Cycle power by closing the main
circuit breaker.
Same as above
Repair leak, recharge with type and
amount of refrigerant specified on
serial tag. Cycle power by closing
the main circuit breaker.
Does not cool
Cooling exceeds capacity of chiller
Microprocessor programmed
incorrectly
Loss of refrigerant
Relay or coil failure
Thermal expansion valve open too
much or malfunctioning
Hot gas bypass valve not
functioning properly
Reduce cooling load
Reprogram microprocessor
Repair leak and recharge with type
and amount of refrigerant specified
on serial tag
Replace relay or coil
Replace or adjust thermal
expansion valve
Call Lydall