CE Declaration of Conformity
Lydall Industrial Thermal Solutions declares that the Lydall product referred to in this manual is in
conformity with the provisions of:
Council Directive 2004/108/EC (Electromagnetic Compatibility Directive)
European Standards:
EN55011, Group 1, Class A
EN61326, Industrial Requirements
and
Council Directive 2006/95/EC (Low Voltage Directive)
European Standard:
EN60204-1
A signed declaration of conformity is available from Lydall upon request.
European Directive 97/23/EC
As of May 29, 2002, the European pressure equipment directive (PED) 97/23/EC became
mandatory for the CE marking of some pressure equipment. Lydall chillers and condensing units
are not CE marked to the PED. Most Lydall chillers fall into the Category I or the Sound
Engineering Practice categories as defined by the PED and since chillers fall under the Low Voltage
Directive (
2006/95/EC
), they are excluded from the scope of the PED per Article 1, paragraph 3.6
of the PED. Some chillers and condensing units using hermetic compressors of 7.5 HP or more
that are classified as Category II are not excluded from the PED. In these cases, it is the
responsibility of the end-user to assure that the final installation complies with all of the appropriate
European directives including the PED. For more information regarding the PED and other
European directives, go to http://www.newapproach.org/
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com