1. GENERAL INFORMATION
•
This appliance is a sealed electric radiator.
•
This appliance conforms to the standards en 60 335-1
and en 60 335-2-30.
•
This appliance is class 1 and has a protection level ip44.
•
This appliance complies with the european directive
2004/108/eC (Ce marking on all appliances).
•
KABA p:
- Radiator for wall mounting or freestanding positioning.
- for 230 v – 50 hz supply.
- supplied with 3 core cable and fitted with an earthed
plug, wall brackets, screws and feet.
•
KABA:
- Radiator for wall mounting.
- for 400 v – 50 hz supply.
- supplied with 3 core cable, wall brackets and screws.
2. INSTALLATION
pOSITIONING
•
The radiator must be positioned horizontally in order
for it to function correctly.
•
The radiator must be positioned according to the
applicable standards and the minimum distances as
specified in picture 1 should be carefully observed.
•
if installed in a bathroom (picture 2), the radiator must
be positioned “outside” volume 2, insofar as no operating
controls (button, switch, etc …) are in reach of persons in
the bath or under the shower.
•
The radiator must be fixed to the wall using the wall
brackets supplied with the radiator and shall not be
located underneath an electrical socket.
FIxING
•
mark out the distance between the brackets and the
positions for the screw holes as shown in the table in
picture 3a.
•
insert the safety clips in the wall brackets as shown in
picture 3b.
•
for the correct installation of radiators it is essential that
the fixing of the radiator is carried out in such a way that
it is suitable for intended use And predictable misuse.
A number of elements need to be taken into
consideration including the fixing method used to
secure the radiator to the wall, the type and condition
of the wall itself, and any additional potential forces or
weights, prior to finalizing installation.
•
The fixing materials provided are only intended for
installation on walls made of solid wood, bricks, concrete
or on timber-frame stud walls where the fixing is into
the timber. All walls being considered should have no
more than a maximum of 3 mm wall finishing. for walls
made of other materials, for example hollow bricks;
please consult your installer and/or specialist supplier.
In all cases it is strongly recommended that a suitably
qualified professional installer or similar tradesperson
carries out the installation.
•
The KABA p radiator can alternatively be fitted with
feet for freestanding use. fit the feet supplied with the
radiator by pressing them on to the radiator, as shown
in figure 3d.
CONNECTION
•
The electrical installation must comply with local or
national regulations.
•
The radiator must be connected to the electrical supply
using the supply cable fitted to the unit using a switched
fused spur having 3mm separation on all poles.
•
if the radiator is installed in a bathroom or shower room,
it must be protected with a residual current device (RCd)
with a rated residual current not exceeding 30 mA.
•
The radiator should be connected by a suitable and
qualified electrician. please refer to the table hereunder
for the connection of the radiator.
VOLTAGE
230 V(*)
400 V
LIVE 1
Brown wire
Brown wire
LIVE 2
-
Grey wire
NEUTRAL
Blue wire
-
EARTH
Green/Yellow wire
Green/Yellow wire
(*) 230 vAC delivered with cable fitted with schuko plug
3. OpERATION
•
The radiator is switched on by setting the switch in
position i (figure 4 A). The required room temperature
GB
GeneRAl
INFORMATION
|
26
LVI0019_Manual Kaba_ZW_v5.indd 26
17-01-14 09:47
Summary of Contents for KABA
Page 9: ...9 pRodUCT INFORMATION 3C 3B 1 2 3 4 5 3D LVI0019_Manual Kaba_ZW_v5 indd 9 17 01 14 09 47 ...
Page 10: ...pRodUCT INFORMATION 10 4 5 D B C A LVI0019_Manual Kaba_ZW_v5 indd 10 17 01 14 09 47 ...
Page 11: ...KABA LVI0019_Manual Kaba_ZW_v5 indd 11 17 01 14 09 47 ...
Page 28: ...Notes notes 28 LVI0019_Manual Kaba_ZW_v5 indd 28 17 01 14 09 47 ...
Page 29: ...29 NOTES notes LVI0019_Manual Kaba_ZW_v5 indd 29 17 01 14 09 47 ...
Page 32: ...LVI0019_Manual Kaba_ZW_v5 indd 32 17 01 14 09 47 ...