background image

Trouble Shooting

Please check to make sure the instructions are followed exactly before attempting trouble shooting of the 
appliance.

Warning:

  Trouble shooting and servicing of gas and electrical devices of the appliance should only be 

conducted by a qualified service technician.

Caution:

  Label all wires prior to disconnection when servicing controls.  Wiring errors cause improper 

and dangerous operation.  Verify proper operation after servicing. 

Problem

Pilot will not light after 
pressing the sparker 
many times.

Pilot will not remain 
on after being lit.

Possible Cause

Air in gas line.

No gas supply.

Piezo wire loose

Defective Piezo

Piezo wire grounding

Electrode grounding

Electrode gap incorrect

Poor Pilot flame

Faulty Thermopile

Faulty Thermocouple

Loose TP-THTP wire on 
gas valve

Faulty gas valve

Faulty wall or unit 

on/off

 

switch

Corrective Action

Purge air from gas line.

Check to make sure the gas supply to the appliance is 
turned on and there is adequate gas supply pressure to 
the appliance.

Check for sparks between the spark electrode and the 
pilot head when the sparker is pressed.  If there are no 
sparks:

Check for  broken or poor connection from the sparker to 
the electrode.

Check for the spark shorting or arcing at other locations.

Check for defective piezo

Check for defective or cracked electrode.  With the door 
removed, try lighting the pilot with a match.
Note:  If there is no gas or air coming out of the pilot and 
there is gas pressure to the appliance, the pilot orifice 
may be blocked or the gas valve maybe defective.

Check to see if the pilot flame is large enough to reach 
and surround the thermocouple.  If the flame is too small, 
check for correct gas supply pressure.  If pressure is 
good, adjust  the pilot flame size with the adjustment 
screw on the valve.  If the flame cannot be adjusted, 
there might be some debris obstructing the pilot orifice.

Check for correct millivolts at the thermopile.  The 
thermopile should generate at least 250 mV.

Check for correct millivolts at the thermocouple.   The 
thermocouple should generate at least 30 mV.

Check for poor connection of the thermocouple and 
thermopile to the valve.  If readings are correct for the 
thermopile and thermocouple, replace gas valve.

Note: This is very rare and faults blamed on the gas 
valve are usually incorrect.

Place jumper wire across terminals TP-THTP, if burner 
comes on, this will indicate you have a poor connection 
or faulty appliance on/off switch, wall switch or wall 
thermostat.

Page 18

Summary of Contents for LBV-3

Page 1: ...e fire department PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLING AND OPERATING THE APPLIANCE WARNING If the information in these instructions are not followed exactly a fire or explosion may res...

Page 2: ...s been converted for use with a gas fireplace insert only and can not be used for burning wood or solid fuels unless all original parts have been replaced and the fireplace re approved by the authorit...

Page 3: ...ks FOR YOUR SAFETY Read before lighting DO NOT Use tools to operate controls Use only you hand to push in and turn controls DO NOT Abuse glass doors by striking or slamming shut DO NOT Clean the appli...

Page 4: ...ance of severe burning or the possible ignition of clothing Young children should be carefully supervised when they are in the same room as the appliance Due to the high temperatures the fireplace sho...

Page 5: ...isted and certified for the installation in the U S A and Canada under the following standards ANSI Z21 88b CSA 2 33b 2003 Heater Rated 72 minimum without the fan Please contact CFH Mfg Inc if you hav...

Page 6: ...es not interfere with install dimension or vent pipe If mantle is combustible see below for allowable clearances Note The model Luxor is certified without requiring a hearth projection although local...

Page 7: ...x Slide unit into the opening taking care not to damage the liner allow enough slack for final surround assembly WARNING Failure to position the parts in accordance with these diagrams or failure to u...

Page 8: ...below for allowable clearances A B C Note Measurement taken from under side of mantel to finished floor surface that the unit is sitting on Page 6 9 Note The model Luxor is certified without requiring...

Page 9: ...undisturbed airflow hits the outside vent terminal from any direction The figure below shows minimum vent cap clearances Check local codes for allowable vertical vent terminations Venting notes Where...

Page 10: ...amage or personal injury Vent Installation IMPORTANT This appliances venting system requires room air for combustion which means that there should be provision to allow room air to be used in the comb...

Page 11: ...oor to unhook assembly from the top clips Window Replacement Locate the top door channel over the top firebox relief brackets Locate the bottom two clasps and close clasps Pull the top of the window f...

Page 12: ...grounded three prong receptacle Do not cut or remove the grounding prong from this plug CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dan...

Page 13: ...pliance supply connection the fitter shall provide an easily accessible manual shut off valve The gas supply pipe should enter the appliance case through the opening at the right side The supply pope...

Page 14: ...djustment Air adjustment is located beneath the firebox which is attached to the valve tray This venturi adjustment allows for fine tuning of the flame characteristics which may vary due to climate al...

Page 15: ...rner The second segment is to sit on the small shelf at the rear of the firebox while leaning the burnt end up on the first segment as shown Lean the third segment against the top of the second segmen...

Page 16: ...stallation pictures are with the optional Brick Set installed If you do not have the 3 piece brick set the background will be black Installation of 3 Piece Brick Set The brick sets are pre cut and sli...

Page 17: ...sembly LDBV DR 5 Door Assembly LDBV DR 6 Door Assembly Fan Components FF 101Fan kit FF 102 Heat Sensor Log Set SIT Pilot Assembly Variable Speed Fan Parts List Page 15 WARNING Failure to position the...

Page 18: ...ion carefully 2 Set the thermostat to the lowest setting 3 Controls are accessed by opening the bottom louver 4 Turn the manual burner switch to the OFF position 5 Push in gas control knob slightly an...

Page 19: ...regularly as soon as you notice the buildup white film If the film is left for a longer period of time build up will bake on Once baked it is much harder if not impossible to remove 2 Never use an ab...

Page 20: ...r poor connection from the sparker to the electrode Check for the spark shorting or arcing at other locations Check for defective piezo Check for defective or cracked electrode With the door removed t...

Page 21: ...correct venting Incorrect aeration adjustment No power supply Thermal snap switches loose or defective Loose electrical connection Defective speed controller Defective blower Problem Frequent pilot ou...

Page 22: ...material etc It is imperative that control compartments burners and circulating passage ways of the appliance to be kept clean To clean the logs use a soft paint brush and to clean the burner compartm...

Page 23: ...h respect to the Luxor Limited Lifetime Warranty CFH Mfg Inc may at its discretion fully discharge all obligations with respect to this warranty by refunding to the original warranted purchaser the wh...

Reviews: