2.3 Technical data
2.3.1 LOCC-Box-Net (Control unit)
Input
Nominal voltage
DC 12/24V
Voltage range
DC 10 – 32V
Nominal current
DC 10A max.
System current
DC 40A via copper bar 3x10mm
Polarization protection
internal electronic
Terminal
screw less contact slide
Remote input (SET/RESET)
Signal level
DC 12/24V (EN 61131)
Switch off time (Reset)
> 100ms, < 800ms (falling edge) #
Switch on time (Set)
≥ 1sec (falling edge) #
Output
Switching technology
MosFET
Output current
DC 10A max.
Voltage drop
< 170mV (10A)
Status indication
green, red (see chapter 2.1.3)
Switch on capacity
10.000 μF
Rated switch off current
DC 1A – DC 10 A (via switch, in steps of 1A)
Switch off times
1= fast acting, 2= middle acting, 3=slow acting_1, 4=slow acting_2,
5 - 9= slow acting_3, Curve 10 is via LOCC-Pads programmable!
Status output
Switch technology
Solid state, open Collector with pull up resistor
Signal level
DC 12/24V no fault; DC 0V fault occurred
General Data
Housing material
PA 6.6 (UL 94 V0; NFF I2,F2)
Mounting
snap on TS 35 (acc. EN 50022)
Protection level
IP 20
Mounting position
any
Installation technology
spring termination 0.25mm
2
– 2.5mm
2
all types of wires
until 2.5mm² without end sleeve, until 1.5mm² with end sleeve
Operation temperature
-25°C … +50°C
Store temperature
-40°C … +85°C
Dimension (WxHxD)
8.1mm x 116mm x 114,5mm
Weight
0.12 kg
Approvals
cULus 508, files E135145, vol. 2, sec. 8
Standards
EN 60950-1; EN61131-1,2; EN 60898; EN 60947-4-1; EN 50081