Step by Step instructions for GRAFIK Eye Dimming Panel
4
Mount Wallboxes
and Panels
STEP 2:
Mount Panels
(continued)
GP3, 4
(Suggested Mounting)
Front View
Side View
Front View
Side View
GP8 through 24
(Suggested Mounting)
12" (305 mm)
Minimum
Clearance
to Any
Obstruction
12" (305 mm)
MIN.
Ceiling
Wiring Raceway
Feed
Wiring
Load Wiring
Air
Flow
12" (305 mm)
Minimum
Clearance
to Any
Obstruction
Wall
Wall
Air
Flow
Notes:
■
Panel generates heat. Mount only where ambient temperature will
be 0 °C-40 °C (32 °F-104 °F).
■
Reinforce wall structure as required for weight and local codes.
■
Panel clearances are 12" (305 mm) above and below and 0" to
each side. (allow room for Class 2/PELV clearance).
■
Indoor Use Only. NEMA, Type 1 enclosure, IP2O.
■
Relative Humidity < 90% non-condensing.
■
GP Panels must be mounted within 7° of true vertical.
Ceiling
Weight w/o Packaging
30 lbs (14kg)
115 lbs (52kg)
130 lbs (59kg)
145 lbs (66kg)
160 lbs (73kg)
175 lbs (80kg)
Panel
GP3,4
GP8
GP12
GP16
GP20
GP24
Max BTUs/Hr.
685
1365
2045
2725
3405
4085
Wiring Raceway
Load
Wiring
Feed Wiring
Class 2/PELV wiring
to controls
Class 2/PELV
wiring to controls
Warning!
CE marked panels with 10A circuit breakers
are intended for industrial or commercial installations.
Caution!
Dimming Panels will hum slightly and
internal relays will click while in operation. Mount where
audible noise is acceptable.
Caution!
Mount panel so line (mains) voltage wiring
will be at least 6 feet (1.8 m) from sound or electronic
equipment and its wiring.
Caution!
This equipment is air-cooled. Vents must not
be blocked or you will void the warranty.
Air
Flow
Air
Flow
?
GP8 24
GP3,4
12" (305 mm)
MIN.