Reference Sheets for GRAFIK Eye Dimming Panel
30
Assign Link Hierarchy (2Link only)
Link Hierarchy is only used when there are two control links. Each
circuit can be assigned to a hierarchy listed below (see job prints if
predetermined)
Options
If you are not sure if you have a 2Link Circuit Selector,please call the
Lutron Technical Assistance Hotline at 1-800-523-9466.
Code
A
b
A1
A2
b1
b2
Ab1
Ab2
Definition
Link A only.
Link B only.
Link A unless Link B is present.
Link A unless Link B is present and
Zone X intensity on Link B is >50%.
Link B unless Link A is present.
Link B unless Link A is present and
Zone X intensity on Link A is >50%.
Highest intensity of the zone
assignments of Link A and Link B.
Lowest intensity of the zone
assignments of Link A and Link B.
Primary Link
A
b
A
A
b
b
A
A
Secondary Link
None
None
b
b
A
A
b
b
Application Example
Circuit to follow Link A (standard operation).
Panel is shared by two links to save on Panel costs.
When the DMX-512 Stageboard is plugged in on Link B,
listen to Link B. Return to Link A when the DMX-512
Stageboard is unplugged.
Redundant system. If Link B fails, circuits follow Link A.
DMX-512 Stageboard is plugged in on Link B, but does not
take control until the light intensity of Zone X on Link B is
above 50%.
Redundant system. If Link A fails, circuits follow Link B.
DMX-512 Stageboard plugged in on Link B, but is not given
control until the light intensity of Zone X on Link A is below
50%.
Redundant system. If either Link A or Link B fails, the other
will have higher intensities.
Energy management.