Step by Step Instructions for GRAFIK Eye Dimming Panel
5
Wire System
Incorrect: Branch or Home Run not acceptable
GP
PANEL
GP
PANEL
To other panels, GRX-4000 Series Control Units,
Wallstations, or Control Interfaces.
Control
Interface
GRX-4000
Wallstation
STEP 3:
Control Wiring
Control Link Specifications
Questions on wiring?
Lutron may be able to help with charts of Wallstations
versus distance.
?
Total length of Control Link may be no more than 2,000 feet. This
distance is based on proper shielding on the twisted shielded pair,
and on #12 AWG wire on the wires to terminal 1 and terminal 2 of
the Control Link. If unapproved cable or smaller wire is used, this
limit is affected:
Total number of Wallstations, Control Units, Control Interfaces or
Circuit Selectors = 33 maximum.
Total number of Control Unit addresses = 8 maximum
Note:
GRX-4116/4516 has 2 addresses
GRX-4124/4524 has 3 addresses
Total number of Wallstation or Control Interface addresses = 16
maximum.
Notes:
■
Make wire connections inside the wallbox and GP panel or in a
junction box (by others) within 8 ft. (2.4 m) of the terminal.
■
All control wiring is Class 2/PELV. Do not place any of these
wires in with line voltage (mains voltage) wiring.
■
The order of controls within the control wiring is not important.
450 m (1500 ft.)
2000 ft (600 m) maximum
Correct: Daisychain OK
Terminal 1 & 2
Wires Sizes
#12 AWG
#14 AWG
#16 AWG
#18 AWG
Terminal 1 & 2
Wires Sizes
#12 AWG
2.5 mm
2
1.0 mm
2
GRX-4000
GRX-4000
Control
Interface
Wallstation
Max. Control
Link Length
2000 ft. (600 m)
1400 ft. (425 m)
900 ft. (275 m)
600 ft. (180 m)
Max. Control
Link Length
600 m (2000 ft.)
450 m (1500 ft.)
200 m (650 ft.)